Overtorque Trip/Alarm Level (negative torque)

Overvoltage Stall Level

 

 

 

 

Overtorque Trip/Alarm Level (negative torque)

 

 

Program

Protection Settings

Overtorque Trip/Alarm Level

Parameter Type — Numerical

 

 

 

 

 

 

(negative torque)

 

 

Factory Default — 150.0

 

 

 

 

 

 

 

This parameter sets the torque threshold level that is used as a setpoint for

Changeable During Run — No

 

overtorque tripping during regeneration. This setting is a percentage of the

 

 

 

maximum rated torque of the ASD.

 

Minimum — 0.00

 

 

 

 

 

 

Maximum — 250.0

 

 

 

 

 

 

Units — %

 

 

 

 

Overtorque Trip/Alarm Level (positive torque)

 

 

Program

 

Protection Settings

 

Overtorque Trip/Alarm Level

Parameter Type — Numerical

 

(positive torque)

 

 

Factory Default — 150.0

 

 

 

 

 

 

 

This parameter sets the torque threshold level that is used as a setpoint for

Changeable During Run — No

 

overtorque tripping. This setting is a percentage of the maximum rated torque

 

 

 

of the ASD.

 

 

 

Minimum — 0.00

 

 

 

 

 

 

Maximum — 250.0

 

 

 

 

 

 

Units — %

 

 

 

 

 

 

Overvoltage Stall

 

 

 

 

Program

 

Protection Settings

 

Overvolt Stall

Parameter Type — Selection List

 

This parameter Enables/Disables the Overvoltage Stall function.

Factory Default — Disabled

 

 

 

When enabled, this function causes the ASD to extend the decel time when the

Changeable During Run — Yes

 

DC bus voltage increases due to transient voltage spikes, regeneration, supply

 

 

voltage out of specification, etc. in an attempt to reduce the bus voltage.

 

 

Settings:

 

 

 

 

 

 

Enabled

 

 

 

 

 

Disabled

 

 

 

 

 

Enabled(Forced Shorted Deceleration)

 

 

Overvoltage Stall Level

 

 

 

 

Program

 

Protection Settings

 

Overvoltage Stall Level

Parameter Type — Numerical

 

This parameter sets the upper DC bus voltage threshold that, once exceeded,

Factory Default — (ASD-dependent)

 

 

 

will cause an Overvoltage Stall. An Overvoltage Stall increases the output

Changeable During Run — Yes

 

frequency of the ASD during deceleration for a specified time in an attempt to

 

 

 

prevent an Overvoltage Trip.

 

 

Minimum — 50.0

 

If the overvoltage condition persists for over 4 mS, an Overvoltage Trip will

Maximum — 250.0

 

be incurred.

 

 

 

 

 

 

 

 

 

 

Units — %

94

Note: Thisfeature may increasedeceleration times.

W7 ASD Installation and Operation Manual

Page 100
Image 100
Toshiba W7 Overtorque Trip/Alarm Level negative torque, Overtorque Trip/Alarm Level positive torque, Overvoltage Stall