Overtorque Trip/Alarm Level (negative torque) | Overvoltage Stall Level | |||||
|
|
| ||||
| Overtorque Trip/Alarm Level (negative torque) |
| ||||
| Program | ⇒ | Protection Settings | ⇒ | Overtorque Trip/Alarm Level | Parameter Type — Numerical |
|
|
|
|
| ||
| (negative torque) |
|
| Factory Default — 150.0 | ||
|
|
|
|
|
| |
| This parameter sets the torque threshold level that is used as a setpoint for | Changeable During Run — No | ||||
| overtorque tripping during regeneration. This setting is a percentage of the | |||||
|
| |||||
| maximum rated torque of the ASD. |
| Minimum — 0.00 | |||
|
|
|
|
|
| Maximum — 250.0 |
|
|
|
|
|
| Units — % |
|
|
| ||||
| Overtorque Trip/Alarm Level (positive torque) |
| ||||
| Program |
| Protection Settings |
| Overtorque Trip/Alarm Level | Parameter Type — Numerical |
| (positive torque) |
|
| Factory Default — 150.0 | ||
|
|
|
|
|
| |
| This parameter sets the torque threshold level that is used as a setpoint for | Changeable During Run — No | ||||
| overtorque tripping. This setting is a percentage of the maximum rated torque | |||||
|
| |||||
| of the ASD. |
|
|
| Minimum — 0.00 | |
|
|
|
|
|
| Maximum — 250.0 |
|
|
|
|
|
| Units — % |
|
|
|
|
| ||
| Overvoltage Stall |
|
|
| ||
| Program |
| Protection Settings |
| Overvolt Stall | Parameter Type — Selection List |
| This parameter Enables/Disables the Overvoltage Stall function. | Factory Default — Disabled | ||||
|
| |||||
| When enabled, this function causes the ASD to extend the decel time when the | Changeable During Run — Yes | ||||
| DC bus voltage increases due to transient voltage spikes, regeneration, supply |
| ||||
| voltage out of specification, etc. in an attempt to reduce the bus voltage. |
| ||||
| Settings: |
|
|
|
|
|
| Enabled |
|
|
|
| |
| Disabled |
|
|
|
| |
| Enabled⇒(Forced Shorted Deceleration)⇒ |
| ||||
| Overvoltage Stall Level |
|
|
| ||
| Program |
| Protection Settings |
| Overvoltage Stall Level | Parameter Type — Numerical |
| This parameter sets the upper DC bus voltage threshold that, once exceeded, | Factory Default — | ||||
|
| |||||
| will cause an Overvoltage Stall. An Overvoltage Stall increases the output | Changeable During Run — Yes | ||||
| frequency of the ASD during deceleration for a specified time in an attempt to | |||||
|
| |||||
| prevent an Overvoltage Trip. |
|
| Minimum — 50.0 | ||
| If the overvoltage condition persists for over 4 mS, an Overvoltage Trip will | Maximum — 250.0 | ||||
| be incurred. |
| ⇒ |
| ||
|
|
|
| |||
|
| ⇒ |
|
| Units — % | |
94 | Note: This⇒feature may increase⇒deceleration times. | W7 ASD Installation and Operation Manual |