ST Signal Selection

ST Terminal

ST Signal Selection

Program Terminal Settings Input Terminals Other ST Signal

Selection⇒⇒⇒

This parameter is used to set the operation of the Standby (ST) control terminal or any terminal configured as the ST terminal.

Settings:

ST-to-CC Required

ST-to-CC Not Required

Interlock with F/R Terminal

The setting ST-to-CC Required enables the ASD for operation so long as the control terminal ST is connected to CC via a jumper, contact, or other means.

The ST-to-CC Not Required setting allows the ASD to operate without the ST-to-CCconnection. The control terminal ST may be configured for other functions.

The Interlock with F/R Terminal setting configures the F (Forward) and R (Reverse) control terminals for the secondary function of Standby. Closing a set of contacts to either F or R will cause the ASD to accelerate the motor to the programmed setpoint of F or R. Opening the F and R contact will disable the ASD and the motor will coast to a stop. The control terminal ST may be configured for other functions.

Parameter Type — Selection List Factory Default — ST – CC Required Changeable During Run — No

ST Terminal

Program Terminal Settings Input Terminals ST

This parameterselects the functionalityof the ST discreteinput terminal. In addition, the input terminal must be specified as Normally Open or Normally Closed.

This parameter sets the programmable ST terminal to 1 of the 69 possible functions that are listed in Table 6 on page 138.

128

Parameter Type — Selection List

Factory Default — Standby

Changeable During Run — No

W7 ASD Installation and Operation Manual

Page 134