ST Signal Selection | ST Terminal |
ST Signal Selection
Program Terminal Settings Input Terminals Other ST Signal
Selection⇒⇒⇒⇒
This parameter is used to set the operation of the Standby (ST) control terminal or any terminal configured as the ST terminal.
Settings:
Interlock with F/R Terminal
The setting
The
The Interlock with F/R Terminal setting configures the F (Forward) and R (Reverse) control terminals for the secondary function of Standby. Closing a set of contacts to either F or R will cause the ASD to accelerate the motor to the programmed setpoint of F or R. Opening the F and R contact will disable the ASD and the motor will coast to a stop. The control terminal ST may be configured for other functions.
Parameter Type — Selection List Factory Default — ST – CC Required Changeable During Run — No
ST Terminal
Program Terminal Settings Input Terminals ST
This parameter⇒selects the functionality⇒of the ST discrete⇒input terminal. In addition, the input terminal must be specified as Normally Open or Normally Closed.
This parameter sets the programmable ST terminal to 1 of the 69 possible functions that are listed in Table 6 on page 138.
128
Parameter Type — Selection List
Factory Default — Standby
Changeable During Run — No