RES Terminal |
|
|
|
|
| Ridethrough Time | ||
|
|
|
|
|
| |||
RES Terminal |
|
|
|
|
| |||
Program | ⇒ | Terminal Settings | ⇒ | Input Terminals | ⇒ | RES | Parameter Type — Selection List | |
|
|
|
| Factory Default — Reset | ||||
This parameter selects the functionality of the RES discrete input terminal. | ||||||||
| ||||||||
In addition, the input terminal must be specified as Normally Open or | Changeable During Run — No | |||||||
Normally Closed. |
|
|
|
|
| |||
This parameter sets the programmable RES terminal to 1 of the 69 possible |
| |||||||
functions that are listed in Table 6 on page 138. |
|
|
| |||||
|
|
|
|
|
| |||
RES Terminal Delay |
|
|
|
|
| |||
Program | ⇒ | Terminal Settings |
| Terminal Delays | Input Terminal | Parameter Type — Numerical | ||
Delays |
| ⇒⇒ |
| |||||
RES Terminal Delay |
|
|
| Factory Default — 8.0 | ||||
This parameter delays the response of the ASD to any change in the RES | Changeable During Run — No | |||||||
terminal input by the programmed value (see waveforms at F Terminal Delay). |
| |||||||
The delay may be increased to provide additional electrical noise immunity or | Minimum — 2.0 | |||||||
to prevent the ASD from responding to contact bounce or chatter. | Maximum — 200.0 | |||||||
|
|
|
|
|
|
| Units — mS | |
Ridethrough Mode |
|
|
|
|
| |||
Program |
| Protection Settings | Ridethrough Mode | Parameter Type — Selection List | ||||
Enables/Disables the Ridethrough function. |
|
| Factory Default — Disabled | |||||
|
|
| ||||||
In the event of a momentary power outage or a make/break at | Changeable During Run — Yes | |||||||
enabled, the Ridethrough function uses regenerative energy to maintain the |
| |||||||
control circuitry settings. |
|
|
|
|
| |||
Regenerated energy is not used to drive the motor. |
|
|
| |||||
|
|
|
|
|
| |||
Ridethrough Time |
|
|
|
|
| |||
Program | ⇒ | Protection Settings | Ridethrough Time | Parameter Type — Numerical | ||||
|
| ⇒ |
|
| Factory Default — 2.00 | |||
⇒ |
|
|
|
|
| |||
In the event of a momentary power outage, this parameter determines the length |
| |||||||
of the Ridethrough time. During a Ridethrough, regenerative energy is used | Changeable During Run — Yes | |||||||
to maintain the control circuitry settings; it is not used to drive the motor. | ||||||||
| ||||||||
The Ridethrough will be maintained for the number of seconds set using this | Minimum — 0.00 | |||||||
Maximum — 320.0 | ||||||||
parameter. |
|
|
|
|
| |||
|
|
|
|
|
| |||
Note: The⇒actual Ridethrough Time⇒is | Units — Seconds |
106 | W7 ASD Installation and Operation Manual |