Toshiba W7 manual RES Terminal Delay, Ridethrough Mode, Ridethrough Time

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 112
Image 112

RES Terminal

 

 

 

 

 

Ridethrough Time

 

 

 

 

 

 

RES Terminal

 

 

 

 

 

Program

Terminal Settings

Input Terminals

RES

Parameter Type — Selection List

 

 

 

 

Factory Default — Reset

This parameter selects the functionality of the RES discrete input terminal.

 

In addition, the input terminal must be specified as Normally Open or

Changeable During Run — No

Normally Closed.

 

 

 

 

 

This parameter sets the programmable RES terminal to 1 of the 69 possible

 

functions that are listed in Table 6 on page 138.

 

 

 

 

 

 

 

 

 

RES Terminal Delay

 

 

 

 

 

Program

Terminal Settings

 

Terminal Delays

Input Terminal

Parameter Type — Numerical

Delays

 

⇒⇒

 

RES Terminal Delay

 

 

 

Factory Default — 8.0

This parameter delays the response of the ASD to any change in the RES

Changeable During Run — No

terminal input by the programmed value (see waveforms at F Terminal Delay).

 

The delay may be increased to provide additional electrical noise immunity or

Minimum — 2.0

to prevent the ASD from responding to contact bounce or chatter.

Maximum — 200.0

 

 

 

 

 

 

 

Units — mS

Ridethrough Mode

 

 

 

 

 

Program

 

Protection Settings

Ridethrough Mode

Parameter Type — Selection List

Enables/Disables the Ridethrough function.

 

 

Factory Default — Disabled

 

 

 

In the event of a momentary power outage or a make/break at ST-to-CC, when

Changeable During Run — Yes

enabled, the Ridethrough function uses regenerative energy to maintain the

 

control circuitry settings.

 

 

 

 

 

Regenerated energy is not used to drive the motor.

 

 

 

 

 

 

 

 

 

Ridethrough Time

 

 

 

 

 

Program

Protection Settings

Ridethrough Time

Parameter Type — Numerical

 

 

 

 

Factory Default — 2.00

 

 

 

 

 

In the event of a momentary power outage, this parameter determines the length

 

of the Ridethrough time. During a Ridethrough, regenerative energy is used

Changeable During Run — Yes

to maintain the control circuitry settings; it is not used to drive the motor.

 

The Ridethrough will be maintained for the number of seconds set using this

Minimum — 0.00

Maximum — 320.0

parameter.

 

 

 

 

 

 

 

 

 

 

 

Note: Theactual Ridethrough Timeis load-dependent.

Units — Seconds

106

W7 ASD Installation and Operation Manual