S12 Terminal |
|
| S3 Terminal | ||
|
|
|
| ||
S12 Terminal |
|
|
| ||
Program | Terminal Settings | Input Terminals | S12 Terminal | Parameter Type — Selection List | |
Assignment |
|
| Factory Default — Unassigned | ||
|
|
|
| ||
This parameter selects the functionality of the S12 discrete input terminal. | Changeable During Run — No | ||||
|
|
|
| ||
Note: The S12 input terminal may be used without the ASD- |
| ||||
Multicom option board. |
|
| |||
Without the |
| ||||
settings will be stored in volatile memory. The terminal |
| ||||
settings will be lost if the system is powered down or reset. |
| ||||
In addition, the input terminal must be specified as Normally Open or |
| ||||
Normally Closed. |
|
|
| ||
This parameter sets the programmable S12 terminal to 1 of the 69 possible |
| ||||
functions that are listed in Table 6 on page 138. |
|
| |||
|
|
|
| ||
|
|
|
| ||
Program | Terminal Settings | Terminal Delays | Input Terminal | Parameter Type — Numerical | |
Delays |
|
| Factory Default — 8.0 | ||
|
|
|
| ||
This parameter delays the response of the ASD to any change in the | Changeable During Run — No | ||||
terminal input⇒by the programmed⇒⇒value (see waveforms at FL Off Delay). | |||||
| |||||
The delay may be increased to provide additional electrical noise immunity or | Minimum — 2.0 | ||||
| |||||
to prevent the ASD from responding to contact bounce or chatter. | Maximum — 200.0 | ||||
|
|
|
| ||
|
|
|
| Units — mS | |
|
|
|
| ||
S2 Terminal |
|
|
| ||
Program | Terminal Settings | Input Terminals | S2 Terminal | Parameter Type — Selection List | |
Assignment |
|
| Factory Default — Preset Speed Cmd #2 | ||
|
|
|
| ||
This parameter selects the functionality of the S2 discrete input terminal. | Changeable During Run — No | ||||
|
|
|
| ||
In addition, the input terminal must be specified as Normally Open or |
| ||||
Normally Closed. |
|
|
| ||
This parameter sets the programmable S2 terminal to 1 of the 69 possible |
| ||||
functions that are listed in Table 6 on page 138. |
|
| |||
|
|
|
| ||
S3 Terminal | ⇒⇒Input Terminals S3 Terminal |
| |||
Program | ⇒Terminal Settings | Parameter Type — Selection List | |||
Assignment⇒ |
|
| Factory Default — Damper Fdbk | ||
|
|
|
| ||
This parameter selects the functionality of the S3 discrete input terminal. | Changeable During Run — No | ||||
|
|
|
| ||
In addition, the input terminal must be specified as Normally Open or |
| ||||
Normally Closed. |
|
|
| ||
This parameter sets the programmable S3 terminal to 1 of the 69 possible |
| ||||
functions that⇒are listed in Table 6⇒⇒on page 138. |
|
| |||
120 | ⇒ | ⇒⇒ |
| W7 ASD Installation and Operation Manual |