Toshiba W7 manual RX Speed Reference Setpoint #1, RX Speed Reference Setpoint #2

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 123
Image 123

RX Speed Reference Setpoint #1

 

 

 

 

RX Speed Reference Setpoint #2

 

 

 

 

RX Speed Reference Setpoint #1

 

 

 

Program

 

Frequency Settings

 

Speed Reference Setpoints

 

RX

Parameter Type — Numerical

Speed Reference Setpoint #1

 

 

 

 

Factory Default — 0.00

 

 

 

 

 

 

 

This parameter is used to set the direction, gain, and bias of the RX input

Changeable During Run — Yes

terminal when the RX terminal is used as the control input while operating in

 

the Speed Control or the Torque Control mode.

 

 

Minimum — -100.0

See RX Speed Frequency Setpoint #1 for further information on this setting

Maximum — 100.0

when used for Speed control.

 

 

 

 

 

 

 

 

 

See RX Torque Reference Setpoint #1 for further information on this setting

Units — %

 

when used for Torque control.

 

 

 

 

 

This parameter sets the RX input level that is associated with RX Speed

 

 

Frequency Setpoint #1 when operating in the Speed control mode or is

 

 

associated with the RX Torque Reference Setpoint #1 when operating in the

 

Torque control mode.

 

 

 

 

 

This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal

 

range.

 

 

 

 

 

 

 

 

 

 

 

RX Speed Reference Setpoint #2

 

 

 

Program

Frequency Settings

Speed Reference Setpoints

RX

Parameter Type — Numerical

range.

 

 

 

 

Speed Frequency Setpoint #2

 

 

 

 

 

 

 

Factory Default — 100.00

This parameter is used to set the direction, gain, and bias of the RX input

Changeable During Run — Yes

terminal when the RX terminal is used as the control input while operating in

 

the Speed Control or the Torque Control mode.

 

 

Minimum — -100.0

See RX Speed Frequency Setpoint #1 for further information on this setting

Maximum — 100.0

when used for Speed control.

 

See RX Torque Reference Setpoint #1 for further information on this setting

Units — %

 

when used for Torque control.

 

This parameter sets the RX input level that is associated with RX Speed

 

Frequency Setpoint #2 when operating in the Speed control mode or is

 

associated with the RX Torque Reference Setpoint #2 when operating in the

 

Torque control mode.

 

This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal

 

W7 ASD Installation and Operation Manual

117

Page 123
Image 123
Toshiba W7 manual RX Speed Reference Setpoint #1, RX Speed Reference Setpoint #2