Toshiba W7 manual ASD Wait Time, ASD Typeform, Autotune Control Setting, Autotune Enable

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 62
Image 62

ASD Wait Time

 

 

 

 

Base Frequency #1

 

 

 

 

 

 

ASD Wait Time

 

 

 

 

 

Program

Special Control

 

Inverter Wait Time

Parameter Type — Read-Only

This parameter determines the amount of time that the drive will wait before

Factory Default — (ASD-dependent)

 

outputting a signal to the motor once the switch-to-drive-output criteria has

Changeable During Run — No

been met.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ASD Typeform

 

 

 

 

 

Program

Utilities Version

 

ASD Type

Parameter Type — Read-Only

This parameter is read-only and displays the current typeform configuration of

Factory Default — (ASD-dependent)

 

the ASD.

 

 

 

 

 

Changeable During Run — No

⇒⇒

 

 

 

 

 

Autotune Control Setting

 

 

 

Program Motor Settings

Autotune Control Setting

Parameter Type — Selection List

When enabled via the Autotune Enable parameter, this parameter sets the

Factory Default — Disabled

 

Autotune command status.

 

 

 

Changeable During Run — No

 

 

 

 

 

 

Settings:

 

 

 

 

 

 

(Autotune) Disabled

 

 

 

 

Reset (Motor) Defaults

 

 

 

 

Enable (Autotune) on Run Command

 

 

 

 

 

 

 

Autotune Enable

 

 

 

 

 

Program

Motor Settings

Autotune Enable

Parameter Type — Selection List

This parameter Enables/Disables the Autotune function.

Factory Default — Enabled

 

 

 

 

Changeable During Run — No

Base Frequency #1

 

 

 

 

Program Motor Settings Base Frequency #1

Parameter Type — Numerical

The Base Frequency setting determines the frequency at which the output

Factory Default — 60.0

 

voltage of the ASD reaches its maximum setting. The maximum voltage setting

Changeable During Run — Yes

cannot be more that the input voltage

(see the Maximum Output Voltage #1

 

parameter). There are four Base Frequency profile settings: #1 – #4.

Minimum — 25.0

Note: For proper motor operation, the Base Frequency is

Maximum — 299.0

normally set for the name-plated frequency of the motor.

Units — Hz

 

 

 

 

 

 

56

W7 ASD Installation and Operation Manual

Page 62
Image 62
Toshiba W7 manual ASD Wait Time, ASD Typeform, Autotune Control Setting, Autotune Enable, Base Frequency #1