Brake Fault Internal Timer

 

 

 

Commercial (Power) Hold Time

 

 

 

 

 

 

Brake Fault Internal Timer

 

 

 

 

 

Program

Protection Settings

Brake Fault Internal Timer

Parameter Type — Numerical

 

Both

 

 

 

 

Factory Default — 0.00

 

After a brake failure has occurred, the user-set Brake Fault Time clock setting

 

 

will begin to count down. Once this time has elapsed, a signal will be provided

Changeable During Run — Yes

 

to indicate that the brake has failed.

 

 

 

 

This signal may be used to halt a related system or to notify the user.

Minimum — 0.00

 

 

 

 

 

 

 

 

Maximum — 10.00

 

 

 

 

 

 

 

 

Units — Seconds

 

Break/Make Auto Restart

 

 

 

 

 

Program

 

Protection Settings

 

Break/Make (Auto Retry)

Parameter Type — Selection List

 

Enables/Disables the ability of the drive to start into a spinning motor when the

Factory Default — Off

 

 

 

ST-to-CCconnection momentarily opens and is then closed (Break/Make ST)

Changeable During Run — No

 

or after a power interruption (momentary power failure).

 

 

 

 

 

Settings:

 

 

 

 

 

 

 

 

Off

 

 

 

 

 

 

 

 

Power Failure

 

 

 

 

 

 

Make/Break ST

 

 

 

 

 

 

 

 

 

 

 

 

Command Mode

 

 

 

 

 

Program

 

Utilities Command and Frequency Settings Command

Parameter Type — Selection List

 

 

⇒⇒

 

 

 

 

Mode Select

 

 

 

 

Factory Default — Terminal Block

 

The Command Mode Selection establishes the source of the command input

Changeable During Run — No

 

for the ASD. Command inputs include Run, Stop, Forward, etc.

 

 

Settings:

 

 

 

 

 

 

 

 

(Use) (Control Terminal Strip) Terminal Block

 

 

 

(Use) LEDKeypad

 

 

 

 

(Use) Common Serial (TTL)

 

 

 

 

 

(Use) RS232/RS485

 

 

 

 

 

(Use) Communication Card

 

 

 

 

 

Commercial (Power) Hold Time

 

 

 

Program

 

Special Control Commercial Hold Time

 

Parameter Type — Selection List

 

This parameter determines the amount of time that the connection to

Factory Default — 2.00

 

commercial power is maintained once the switch-to-drive-output criteria has

Changeable During Run — No

 

been met.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W7 ASD Installation

and OperationManual

 

Minimum — 0.10

 

 

Maximum — 10.00

 

 

Units — Seconds

61

Page 67
Image 67