Preset Speed #1

Preset Speed #2

Preset Speed #1

Program Preset Speeds

1

Up to 15 output frequency values that fall within the Lower Limit and the Upper Limit range may be programmed into the ASD and output as a Preset Speed. This parameter assigns an output frequency to binary number 0001 and is identified as Preset Speed #1. The binary number is applied to S1 S4 of the Control Terminal Strip to output the Preset Speed.

Perform the following setup to allow the system to receive Preset Speed control input at the S1 – S4 terminals:

1.

Program

Utilities Command and Frequency Settings Frequency

 

Mode #1

Use Binary/BCD.

 

 

2.

Program Terminal Settings

Input Terminals S1 (set to Set Speed 1;

 

LSB of 4-bit count). Repeat for S2 S4 Terminals (to the MSB of the 4-bit

 

count) as Set Speed 2 4, respectively (all Normally Open).

Note: The default setting of S4 is EOff, but this terminal may be re-

 

assigned as the MSB. EOFF is a safety feature that should

 

be assigned to another terminal.

 

3.

Program

Preset Speeds

1 (set an output frequency for Preset Speed

 

#1; repeat for Preset Speed 2 15 as required).

 

4.

Program Preset Speeds Mode Enable/Disable.

 

 

When Enabled, the Speed, Direction, Accel/Decel Group, V/f Group,

 

and the Torque Limit Group settings for the active Preset Speed are used

 

(applies to all 1–15).

 

 

 

 

 

When Disabled, only the speed setting of the active Preset Speed is used.

5.

From the Frequency Command screen (only), place the system in the

 

Remote mode (LocalRemote LED Off).

 

 

 

 

 

6.

Provide a Run command (connect F and/or R to CC).

 

Connect S1 to CC to run Preset Speed

#1 (S1 to CC =0001 binary).

With S1 S4 configured to output PresetSpeeds, 0001B – 1111B may be applied to S1 – S4 of the Control Terminal Strip to run the associated Preset Speed of the truth table.

If bidirectional operation is required, F and R must be connected to CC, and the Mode setting must be Enabled for a given Preset Speed being run.

With S1 being the least significant bit of a binary count, the S1 – S4 settings will produce the programmed speed settings as indicated in the truth table to the right.

Parameter Type — Numerical

Factory Default — 60.0

Changeable During Run — Yes

Minimum — Lower Limit

Maximum — Upper Limit

Units — Hz

Preset Speed Truth Table.

PS #

S4

S3

S2

S1

Output

 

 

 

 

 

 

1

0

0

0

1

# 1

 

 

 

 

 

 

2

0

0

1

0

# 2

 

 

 

 

 

 

3

0

0

1

1

# 3

 

 

 

 

 

 

4

0

1

0

0

# 4

 

 

 

 

 

 

5

0

1

0

1

# 5

 

 

 

 

 

 

6

0

1

1

0

# 6

 

 

 

 

 

 

7

0

1

1

1

# 7

 

 

 

 

 

 

8

1

0

0

0

# 8

 

 

 

 

 

 

9

1

0

0

1

# 9

 

 

 

 

 

 

10

1

0

1

0

# 10

 

 

 

 

 

 

11

1

0

1

1

# 11

 

 

 

 

 

 

12

1

1

0

0

# 12

 

 

 

 

 

 

13

1

1

0

1

# 13

 

 

 

 

 

 

14

1

1

1

0

# 14

 

 

 

 

 

 

15

1

1

1

1

# 15

 

 

 

 

 

 

Note: 1=connected to CC.

Preset Speed #2

Program

Preset Speeds

2

100

This parameter assigns an output frequency to binary number 0010 and is identified as Preset Speed #2. The binary number is applied to S1 S4 of the Control Terminal Strip to output the Preset Speed (see Preset Speed #1 for further information on this parameter).

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — Lower Limit

Maximum — Upper Limit

Units — Hz

W7 ASD Installation and Operation Manual

Page 106
Image 106
Toshiba W7 manual Preset Speed #1, Preset Speed #2, Preset Speed Truth Table