R Terminal Delay |
|
|
| Run Frequency Hysteresis | |||
|
|
|
|
| |||
R Terminal Delay |
|
|
|
| |||
Program | ⇒ | Terminal Settings |
| Terminal Delays Input Terminal | Parameter Type — Numerical | ||
Delays |
|
| ⇒⇒ |
| |||
R Terminal Delay |
|
| Factory Default — 8.0 | ||||
This parameter delays the response of the ASD to any change in the R terminal | Changeable During Run — No | ||||||
input by the programmed value. |
|
|
| ||||
The delay may be increased to provide additional electrical noise immunity or | Minimum — 2.0 | ||||||
to prevent the ASD from responding to contact bounce or chatter. | Maximum — 200.0 | ||||||
|
|
|
|
|
| Units — mS | |
Run Frequency |
|
|
|
| |||
Program | ⇒ | Special Control | ⇒ | Run Frequency | Parameter Type — Numerical | ||
|
|
| Factory Default — 0.0 | ||||
This parameter establishes a center frequency (Run Frequency) of a frequency | |||||||
| |||||||
band. |
|
|
|
|
| Changeable During Run — Yes | |
|
|
|
|
|
| ||
The Run Frequency Hysteresis parameter provides a | Minimum — 0.0 | ||||||
the Run Frequency; thus, establishing a frequency band. | |||||||
| |||||||
During acceleration, the ASD will not output a signal to the motor until the | Maximum — Max. Freq. | ||||||
lower level of the band is reached. | Units — Hz | ||||||
During deceleration, the ASD will continue to output the programmed | |||||||
| |||||||
deceleration output signal to the motor until the lower level of the band is |
| ||||||
reached;⇒at which time the output will go to 0.0 Hz. |
| ||||||
Run Frequency Hysteresis |
| ||||||
Program |
| Special Control Run Freq Hysteresis | Parameter Type — Numerical | ||||
This parameter provides a | Factory Default — 0.0 | ||||||
| ⇒ |
| ⇒ |
| Changeable During Run — Yes | ||
|
|
| Minimum — 0.0 | ||||
|
|
| Maximum — 30.0 | ||||
|
|
| Units — Hz |
112 | W7 ASD Installation and Operation Manual |