Maximum Output Voltage #2 |
|
|
|
| Motor 150% Time Limit | |||
|
|
|
|
| ||||
| Maximum Output Voltage #2 |
|
|
| ||||
| Program | ⇒ | Fundamental Parameters Fundamental #2 Maximum | Parameter Type — Numerical | ||||
|
|
|
|
| ⇒⇒ |
| ||
| Output Voltage #2 |
|
|
|
| Factory Default — (ASD dependent) | ||
| This parameter sets the maximum value of the output voltage of the ASD for | Changeable During Run — Yes | ||||||
| the #2 Motor Set. |
|
|
|
|
| ||
| Regardless of the programmed value, the output voltage cannot be higher than | Minimum — 0.0 | ||||||
| the input voltage. |
|
|
|
| Maximum — (ASD dependent) | ||
| The actual output voltage will be influenced by the input voltage of the ASD | Units — Volts | ||||||
| and the Supply Voltage Compensation parameter setting. |
|
| |||||
| Maximum Output Voltage #3 |
|
|
| ||||
| Program | ⇒ | Motor Settings Max Output Voltage #3 | Parameter Type — Numerical | ||||
|
|
| ⇒ |
|
|
| Factory Default — (ASD dependent) | |
| This parameter sets the maximum value of the output voltage of the ASD for |
| ||||||
| the #3 Motor Set. |
|
|
|
| Changeable During Run — Yes | ||
| Regardless of the programmed value, the output voltage cannot be higher than | Minimum — 0.0 | ||||||
| the input voltage. |
|
|
|
|
| ||
| The actual output voltage will be influenced by the input voltage of the ASD | Maximum — (ASD dependent) | ||||||
| and the Supply Voltage Compensation parameter setting. |
| Units — Volts | |||||
| Maximum Output Voltage #4 |
|
|
| ||||
| Program | ⇒ | Motor Settings Max Output Voltage #4 | Parameter Type — Numerical | ||||
|
|
| ⇒ |
|
|
| Factory Default — (ASD dependent) | |
| This parameter sets the maximum value of the output voltage of the ASD for |
| ||||||
| the #4 Motor Set. |
|
|
|
| Changeable During Run — Yes | ||
| Regardless of the programmed value, the output voltage cannot be higher than | Minimum — 0.0 | ||||||
| the input voltage. |
|
|
|
|
| ||
| The actual output voltage will be influenced by the input voltage of the ASD | Maximum — (ASD dependent) | ||||||
| and the Supply Voltage Compensation parameter setting. |
| Units — Volts | |||||
| Mode 1/2 Switching Frequency |
|
|
| ||||
| Program | ⇒ | Frequency Settings Reference Priority | Mode #1/#2 | Parameter Type — Numerical | |||
|
|
|
| ⇒ |
| ⇒ |
| |
| Switching Frequency |
|
|
|
| Factory Default — 1.00 | ||
| This parameter sets the threshold frequency that will be used in the Reference | Changeable During Run — Yes | ||||||
| Priority Selection parameter to determine if Frequency Mode #1 or #2 will |
| ||||||
| control the output of the ASD. |
|
|
| Minimum — 0.10 | |||
|
|
|
|
|
|
|
| Maximum — Max. Freq. |
|
|
|
|
|
|
|
| Units — Hz |
| Motor 150% Time Limit |
|
|
|
| |||
| Program |
| Protection Settings Motor 150% Overload Time Limit | Parameter Type — Numerical | ||||
| This parameter establishes a time that the motor may operate at 150% of its | Factory Default — 600 | ||||||
|
| |||||||
| rated current before tripping. This setting applies the time/150% reference to | Changeable During Run — Yes | ||||||
| the individual settings of each motor (e.g., this setting references 150% of the | |||||||
|
| |||||||
| Thermal Protection setting for the #1 motor). |
| Minimum — 10 | |||||
| The unit will trip sooner than the time entered here if the overload is greater | Maximum — 2400 | ||||||
| than 150%. |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
| ⇒ |
|
| ⇒ |
|
| Units — Seconds |
84 |
|
|
|
|
| W7 ASD Installation and Operation Manual |