Maximum Output Voltage #2

 

 

 

 

Motor 150% Time Limit

 

 

 

 

 

 

Maximum Output Voltage #2

 

 

 

 

Program

Fundamental Parameters Fundamental #2 Maximum

Parameter Type — Numerical

 

 

 

 

 

⇒⇒

 

 

Output Voltage #2

 

 

 

 

Factory Default — (ASD dependent)

 

This parameter sets the maximum value of the output voltage of the ASD for

Changeable During Run — Yes

 

the #2 Motor Set.

 

 

 

 

 

 

Regardless of the programmed value, the output voltage cannot be higher than

Minimum — 0.0

 

the input voltage.

 

 

 

 

Maximum — (ASD dependent)

 

The actual output voltage will be influenced by the input voltage of the ASD

Units — Volts

 

and the Supply Voltage Compensation parameter setting.

 

 

 

Maximum Output Voltage #3

 

 

 

 

Program

Motor Settings Max Output Voltage #3

Parameter Type — Numerical

 

 

 

 

 

 

Factory Default — (ASD dependent)

 

This parameter sets the maximum value of the output voltage of the ASD for

 

 

the #3 Motor Set.

 

 

 

 

Changeable During Run — Yes

 

Regardless of the programmed value, the output voltage cannot be higher than

Minimum — 0.0

 

the input voltage.

 

 

 

 

 

 

The actual output voltage will be influenced by the input voltage of the ASD

Maximum — (ASD dependent)

 

and the Supply Voltage Compensation parameter setting.

 

Units — Volts

 

Maximum Output Voltage #4

 

 

 

 

Program

Motor Settings Max Output Voltage #4

Parameter Type — Numerical

 

 

 

 

 

 

Factory Default — (ASD dependent)

 

This parameter sets the maximum value of the output voltage of the ASD for

 

 

the #4 Motor Set.

 

 

 

 

Changeable During Run — Yes

 

Regardless of the programmed value, the output voltage cannot be higher than

Minimum — 0.0

 

the input voltage.

 

 

 

 

 

 

The actual output voltage will be influenced by the input voltage of the ASD

Maximum — (ASD dependent)

 

and the Supply Voltage Compensation parameter setting.

 

Units — Volts

 

Mode 1/2 Switching Frequency

 

 

 

 

Program

Frequency Settings Reference Priority

Mode #1/#2

Parameter Type — Numerical

 

 

 

 

 

 

 

Switching Frequency

 

 

 

 

Factory Default — 1.00

 

This parameter sets the threshold frequency that will be used in the Reference

Changeable During Run — Yes

 

Priority Selection parameter to determine if Frequency Mode #1 or #2 will

 

 

control the output of the ASD.

 

 

 

Minimum — 0.10

 

 

 

 

 

 

 

 

Maximum — Max. Freq.

 

 

 

 

 

 

 

 

Units — Hz

 

Motor 150% Time Limit

 

 

 

 

 

Program

 

Protection Settings Motor 150% Overload Time Limit

Parameter Type — Numerical

 

This parameter establishes a time that the motor may operate at 150% of its

Factory Default — 600

 

 

 

rated current before tripping. This setting applies the time/150% reference to

Changeable During Run — Yes

 

the individual settings of each motor (e.g., this setting references 150% of the

 

 

 

Thermal Protection setting for the #1 motor).

 

Minimum — 10

 

The unit will trip sooner than the time entered here if the overload is greater

Maximum — 2400

 

than 150%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units — Seconds

84

 

 

 

 

 

W7 ASD Installation and Operation Manual