Motor Capacity (kW) |
|
| Motor Constant #4 | ||||
|
|
|
| ||||
Motor Capacity (kW) |
|
|
| ||||
Program | ⇒ | Motor Settings | ⇒ | Motor Capacity (kW) | Parameter Type — Numerical | ||
|
|
|
| Factory Default — | |||
This | |||||||
| |||||||
|
|
|
|
|
| Changeable During Run — No | |
|
|
|
|
|
| Minimum — 0.10 | |
|
|
|
|
|
| Maximum — | |
|
|
|
|
|
| Units — kW | |
|
|
|
| ||||
Motor Constant #1 |
|
|
| ||||
Program | ⇒ | Motor Settings | ⇒ | Motor Constant #1 (Primary resistance) | Parameter Type — Numerical | ||
|
|
|
| Factory Default — | |||
This parameter is the measurement of the stator resistance and is considered a | |||||||
| |||||||
Motor Constant (unchanging). This value is used in conjunction with other | Changeable During Run — No | ||||||
constants to tune the motor. |
|
| |||||
|
|
| |||||
To use Vector Control, Automatic Torque Boost, or Automatic Energy- | Minimum — 0.0 | ||||||
| |||||||
saving, the Motor Constant setting (motor tuning) is required. | Maximum — 100,000 MΩ | ||||||
|
|
|
|
|
| Units — Ω | |
|
|
|
| ||||
Motor Constant #2 |
|
|
| ||||
Program |
| Motor Settings |
| Motor Constant #2 (Secondary | Parameter Type — Numerical | ||
| ⇒⇒ |
|
| ||||
Resistance) |
|
|
| Factory Default — | |||
This parameter is the measurement of the rotor resistance and is considered a | Changeable During Run — No | ||||||
Motor Constant (unchanging). This value is used in conjunction with other |
| ||||||
constants to tune the motor. |
|
| Minimum — 0.00 | ||||
This setting (motor tuning) is required to use the Vector Control, Automatic | Maximum — Open | ||||||
Torque Boost, or Automatic | Units — Ω | ||||||
Motor Constant #3 |
|
|
| ||||
Program |
| Motor Settings |
| Motor Constant #3 (Exciting | Parameter Type — Numerical | ||
Inductance) |
|
|
| Factory Default — | |||
|
|
|
|
|
| ||
This parameter is used to input the excitation inductance for the motor. This | Changeable During Run — No | ||||||
value is used in conjunction with other constants to tune the motor. | |||||||
| |||||||
This setting (motor tuning) is required to use the Vector Control, Automatic | Minimum — 0.00 | ||||||
| |||||||
Torque Boost, or Automatic | Maximum — 6500.0 | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
| Units — µH | |
|
|
|
| ||||
Motor Constant #4 |
|
|
| ||||
Program |
| Motor Settings |
| Motor Constant #4 (Load Inertia) | Parameter Type — Numerical | ||
This parameter is used to compensate for the affects of load inertia during speed | Factory Default — 1.0 | ||||||
| |||||||
changes. |
|
|
|
|
| Changeable During Run — Yes | |
|
|
|
|
|
| ||
Acceleration and deceleration overshoot may be reduced by increasing this | Minimum — 0.0 | ||||||
value. |
|
|
|
|
| ||
|
|
|
|
|
| ||
This setting (motor tuning) is required to use the Vector Control, Automatic | Maximum — 100.0 | ||||||
Torque Boost⇒⇒, or Automatic |
| ||||||
W7 ASD Installation⇒ | and Operation⇒Manual | 85 |