OUT1 Off Delay

Number of Retries

Program Protection Settings Number of Retries

After a trip has occurred, this parameter sets the number of times that an automatic system restart is attempted for a qualified trip.

The trip conditions listed below will not initiate the Retry function:

• OCA1,2, or 3 (Arm Short Ckt),

• EPH1 (Input Phase Failure),

• EPH0 (Output Phase Failure),

• OCL (Startup Overcurrent),

• EF1 or 2 (Ground Fault),

• EMG (Emergency Off),

• EEP1 (EEPROM Fault),

• Err2 through Err9 (Main RAM/ROM Fault),

E-10 (Sink/Source Error),

• 13 (Speed Error), or

• 17 (Key Error).

See the section titled General Safety Information on pg. 1 for further information on this setting.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 10

ON Terminal

 

Program

Terminal Settings

Input Terminals

ON

Parameter Type — Selection List

 

This parameter selects the functionality of the ON discrete input virtual

Factory Default — Unassigned

 

 

 

terminal.

 

 

 

Changeable During Run — No

 

 

 

 

 

 

As a virtual terminal, the ON control terminal exists only in memory and is

 

 

considered to always be in its True (or connected to CC) state.

 

 

It is often practical to assign this terminal to a function that the user desires to

 

 

be maintained regardless of external conditions or operations.

 

 

This parameter sets the programmable ON terminal to 1 of the 69 possible

 

 

functions that are listed in Table 6 on page 138.

 

 

 

In addition, the input terminal must be specified as Normally Open or

 

 

Normally Closed.

 

 

 

 

 

 

 

 

 

OUT1 Off Delay

 

 

 

 

Program

Terminal Settings

Terminal Delays

Output Terminal

Parameter Type — Numerical

 

Delays

OUT1 OUT1 Off Delay

 

Factory Default — 2.0

 

 

 

 

 

 

Once the condition is met to change the state of the OUT1 (A & C) output

Changeable During Run — No

 

contacts, this parameter delays the response of the contacts by the programmed

 

 

 

value (see waveforms at FL Off Delay).

 

Minimum — 2.0

 

The on andoff delay times of theOUT1 contacts maybe adjusted to provide

Maximum — 200.0

 

more response time to the device that is connected to the output terminals.

 

 

 

⇒⇒⇒

Units — mS