VI/II Torque Reference Setpoint #1 | VI/II Torque Reference Setpoint #2 |
VI/II Torque Reference Setpoint #1
Program Frequency Settings Speed Reference Setpoints VI/II
⇒Perform the⇒following setup to allow⇒the system to perform Torque control⇒ from the VI/II input terminal:
VI/II Torque Reference Setpoint #1
This parameter is used to set the direction, gain, and bias of the VI/II input terminal when the VI/II terminal is used as the control input while operating in the Torque Control mode.
VI/II Input Torque Control Setup
Perform the following setup to allow the system to receive Torque control input at the VI/II input terminal:
• | Program Utilities Command and Frequency Settings Command |
| Mode Select Terminal Block. |
• | Program ⇒Utilities ⇒Command and Frequency Settings ⇒Frequency#1 |
| Mode Select ⇒VI/II. |
• | Provide a Run command (F and/or R). |
Torque Control
• Set VI/II Torque Reference #1,
• Set the VI/II input signal level (VI/II Speed Ref #1) that represents the VI/II Torque Reference #1,
•Set VI/II Torque Reference Setpoint #2, and
•Set the VI/II input signal level (VI/II Speed Ref #2) that represents the VI/II Torque Reference Setpoint #2.
This is accomplished by establishing an associated V/f output pattern for a given VI/II input level.
This parameter sets VI/II Torque Reference #1 and is the output torque value that is associated with the setting of VI/II Speed Reference Setpoint #1 when operating in the Torque control mode.
This value is entered as 0% to 250% of the rated torque.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
Torque Settings
VI/II Torque Reference Setpoint #2
Program | Frequency Settings | Speed Reference Setpoints | VI/II |
⇒ | ⇒ | ⇒ | ⇒ |
VI/II Torque Reference Setpoint #2 |
|
This parameter is used to set the direction, gain, and bias of the VI/II input terminal when the VI/II terminal is used as the control input while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given VI/II input level.
See VI/II Torque Reference Setpoint #1 for further information on this setting.
This parameter sets VI/II Torque Reference Setpoint #2 and is the output torque value that is associated with setting of VI/II Speed Reference Setpoint #2 when operating in the Torque control mode.
This value is entered as 0% to 250% of the rated torque.
136
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
W7 ASD Installation and Operation Manual