VI/II Torque Reference Setpoint #1

VI/II Torque Reference Setpoint #2

VI/II Torque Reference Setpoint #1

Program Frequency Settings Speed Reference Setpoints VI/II

Perform thefollowing setup to allowthe system to perform Torque controlfrom the VI/II input terminal:

VI/II Torque Reference Setpoint #1

This parameter is used to set the direction, gain, and bias of the VI/II input terminal when the VI/II terminal is used as the control input while operating in the Torque Control mode.

VI/II Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input at the VI/II input terminal:

Program Utilities Command and Frequency Settings Command

 

Mode Select Terminal Block.

Program Utilities Command and Frequency Settings Frequency#1

 

Mode Select VI/II.

Provide a Run command (F and/or R).

Torque Control

• Set VI/II Torque Reference #1,

• Set the VI/II input signal level (VI/II Speed Ref #1) that represents the VI/II Torque Reference #1,

Set VI/II Torque Reference Setpoint #2, and

Set the VI/II input signal level (VI/II Speed Ref #2) that represents the VI/II Torque Reference Setpoint #2.

This is accomplished by establishing an associated V/f output pattern for a given VI/II input level.

This parameter sets VI/II Torque Reference #1 and is the output torque value that is associated with the setting of VI/II Speed Reference Setpoint #1 when operating in the Torque control mode.

This value is entered as 0% to 250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 250.0

Units — %

Torque Settings

VI/II Torque Reference Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

VI/II

VI/II Torque Reference Setpoint #2

 

This parameter is used to set the direction, gain, and bias of the VI/II input terminal when the VI/II terminal is used as the control input while operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given VI/II input level.

See VI/II Torque Reference Setpoint #1 for further information on this setting.

This parameter sets VI/II Torque Reference Setpoint #2 and is the output torque value that is associated with setting of VI/II Speed Reference Setpoint #2 when operating in the Torque control mode.

This value is entered as 0% to 250% of the rated torque.

136

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 250.0

Units — %