I/O and Control
The W7 ASD can be controlled by several input types and combinations thereof, as well as operate within a wide range of output frequency and voltage levels. This section describes the ASD control methods and supported I/O functions.
The Control Terminal Strip PCBA (P/N 48570) supports discrete and analog I/O functions.
The Control Terminal Strip is shown in Figure 5 on pg. 20. Table 2 and lists the names, the default settings (where applicable), and the descriptions of the input and output terminals.
Figure 17 on pg. 24 shows the basic connection diagram for the W7 ASD system.
Table 2. Control Terminal Strip default assignment terminal names and functions.
Terminal | Input/Output | Terminal Function | Circuit Config. | |
Name | (default setting if programmable) | |||
|
| |||
|
|
|
| |
ST | Discrete Input | Standby (jumper to CC to operate the unit) — Multifunctional |
| |
programmable discrete input (see Installation Notes on pg. 13 for further |
| |||
|
| information on this terminal). |
| |
|
|
|
| |
RES | Discrete Input | Reset — Multifunctional programmable discrete input. |
|
FDiscrete Input Forward — Multifunctional programmable discrete input.
|
|
| Figure 7 on pg. 23. | |
R | Discrete Input | Reverse — Multifunctional programmable discrete input. | ||
| ||||
|
|
|
| |
S1 | Discrete Input | Preset Speed 1 — Multifunctional programmable discrete input. |
| |
|
|
|
| |
S2 | Discrete Input | Preset Speed 2 — Multifunctional programmable discrete input. |
| |
|
|
|
| |
S3 | Discrete Input | Preset Speed 3 — Multifunctional programmable discrete input. |
| |
|
|
|
| |
S4 | Discrete Input | Emergency Off — Multifunctional programmable discrete input. |
| |
|
|
|
| |
RR | Analog Input | RR — Multifunction programmable analog input | Figure 8 on pg. 23. | |
(0.0 to 10 volt input — 0 to 80 Hz output). Reference CC. | ||||
|
|
| ||
|
|
|
| |
RX | Analog Input | RX — Multifunctional programmable analog input | Figure 9 on pg. 23. | |
|
|
| ||
|
|
|
| |
|
| II — Multifunctional programmable analog input (4 [0] to 20 mADC |
| |
II | Analog Input | input — 0 to 80 Hz output) (see Figure 5 on pg. 20 for the location of the |
| |
|
| II terminal). Reference CC. | Figure 10 on pg. 23. | |
|
|
|
| |
VI | Analog Input | VI — Multifunctional programmable analog input |
| |
(0 to 10 VDC input — 0 to 80 Hz output). Reference CC. |
| |||
|
|
| ||
|
|
|
| |
P24 | DC Output | 24 VDC @ 50 mA output. | Figure 11 on pg. 23. | |
|
|
|
| |
PP | DC Output | PP — 10.0 VDC voltage source for the external potentiometer. | Figure 12 on pg. 23. | |
|
|
| ||
OUT1 | Discrete Output Low Frequency — Multifunctional programmable discrete output. | Figure 13 on pg. 23. | ||
|
|
| ||
OUT2 | Discrete Output Reach Frequency — Multifunctional programmable discrete output. | |||
| ||||
|
|
|
| |
FP | Output | Frequency Pulse — an output pulse train that has a frequency which is | Figure 14 on pg. 23. | |
based on the output frequency of the ASD. | ||||
|
|
| ||
|
|
|
| |
AM | Output | Produces an output current that is proportional to the magnitude of the | Figure 15 on pg. 23 | |
|
| function assigned to this terminal (see Table 8 on page 142). | ||
FM | Output | |||
| ||||
|
|
|
| |
FLC | Output | Fault relay (common). |
| |
|
|
|
| |
FLB | Output | Fault relay (N.C.). | Figure 16 on pg. 23. | |
|
|
|
| |
FLA | Output | Fault relay (N.O.). |
|
CC— Control common (Do Not connect to Earth Gnd).
Discrete Input Terminals On = connected to CC. |
|
Analog Input terminals reference CC. |
|