Cumulative Run-timer Alarm Setting

DC Injection Braking Time

 

 

 

Cumulative Run-timer Alarm Setting

 

 

Program

Protection Settings Cumulative Run-timer Alarm

Parameter Type — Numerical

 

Setting

 

 

 

 

Factory Default — 175.0

 

 

 

 

 

 

 

This parameter sets a run-time value that, once exceeded, provides an output

Changeable During Run — Yes

 

signal. The output signal may be used to control external equipment or used to

 

 

 

engage a brake.

 

 

 

Minimum — 0.1

 

Note: The time displayed is 1/10th of the actual time

Maximum — 999.9

 

(0.1 hr. = 1.0 hr.).

Units — Hours (X 100)

 

 

 

 

 

 

 

 

 

 

DC Injection Braking Current

 

 

Program

Protection DC Injection Current

Parameter Type — Numerical

 

 

 

 

Factory Default — 50.00

 

This parameter sets the percentage of the rated current of the ASD that will be

 

 

used for DC Injection braking. A larger load will require a higher setting.

Changeable During Run — Yes

 

DC Injection Braking

 

Minimum — 0.00

 

DC Injection Braking is a braking system used with three-phase motors.

Maximum — 100.00

 

Unlike conventional brakes, there is no physical contact between the rotating

 

 

shaft and a stationary brake pad or drum. When braking is required, the ASD

Units — %

 

outputs a DC current that is applied to the windings of the motor to quickly

 

 

brake the motor.

The braking currentstops when the time entered in DC

 

 

Injection Braking Time times out.

 

 

The intensity of the DC current used while braking determines how fast the

 

 

motor will come to a stop and may be set at the DC Injection Braking

 

 

Current parameter. The intensity setting is entered as a percentage of the full

 

 

load current of the ASD.

 

 

 

Note: DC Injection Braking is also used to preheat the motor or to

 

 

keep the rotor from spinning freely when no rotation is

 

 

required by providing a pulsating DC current into the motor

 

 

at the Carrier Frequency. This feature may be enabled at the

 

 

Motor Shaft Stationary Control parameter.

 

 

 

 

 

DC Injection Braking Start Frequency

 

 

Program

Protection Settings DC Injection Start Frequency

Parameter Type — Numerical

 

During deceleration this is the frequency at which DC Injection braking will

Factory Default — 0.0

 

start.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changeable During Run — Yes

 

 

 

 

 

 

Minimum — 0.0

 

 

 

 

 

 

Maximum — 120.0

 

 

 

 

 

 

Units — Hz

 

 

 

 

DC Injection Braking Time

 

 

Program

Protection Settings DC Injection Time

Parameter Type — Numerical

 

This parameter is used to set the on-time duration of the DC Injection braking.

Factory Default — 1.00

 

 

 

W7 ASD Installation

and Operation Manual

Changeable During Run — Yes

 

Minimum — 0.00

 

Maximum — 10.00

 

Units — Seconds

65