FM Terminal Assignment

 

 

 

 

 

Frequency Display Resolution

 

 

 

 

 

 

 

 

 

FP Terminal Assignment

 

 

 

 

 

 

 

Program

 

Terminal Settings

 

Output Terminals

FP

FP Terminal

Parameter Type — Selection List

 

Assignment

 

 

 

 

 

Factory Default — Output Frequency

 

 

 

 

 

 

 

 

 

 

This parameter commands the multifunction programmable FP terminal to

Changeable During Run — Yes

 

monitor the value of 1 of 31 possible system functions. As the monitored

 

 

 

function changes in magnitude or frequency, the pulse count of the FP output

 

 

pulse train changes in direct proportion to changes in the monitored function.

 

 

As the monitored value goes up so does the pulse count of the FP output.

 

 

Note: The duty cycle of the output pulse train remains at

 

 

 

65 ±5.0 µS.

 

 

 

 

 

 

 

Possible assignments for this output terminal are listed in Table 8 on page 142.

 

 

 

 

 

 

 

 

 

 

FP Terminal Adjustment

 

 

 

 

 

 

 

Program

Terminal Settings

Output Terminals

FP

FP Terminal

Parameter Type — Numerical

 

 

 

 

 

⇒⇒

 

 

 

Adjustment

 

 

 

 

 

Factory Default — 3.840

 

This parameter sets the full-scale reading of the FP terminal. The full-scale

Changeable During Run — Yes

 

reading of the monitored variable selected in FP Terminal Setting may be set

 

 

here.

 

 

 

⇒⇒

 

Minimum — 1.000

 

 

 

 

 

 

Maximum — 43.200

 

 

 

 

 

 

 

 

 

Units — kHz

 

Frequency Command Panel

 

 

 

 

 

Program

 

System Information and Setup

PID Setup

Frequency

Parameter Type — Numerical

 

Command Panel

 

 

 

 

 

Factory Default — 0.0

 

 

 

 

 

 

 

 

 

 

While operating using PID control, this parameter sets the reference frequency.

Changeable During Run — Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum — 0.0

 

 

 

 

 

 

 

 

 

Maximum — Max. Freq.

 

 

 

 

 

 

 

 

 

Units — Hz

 

 

 

 

 

 

 

Frequency Display Resolution

 

 

 

 

 

Program

 

Utilities Display Attributes

Frequency Display

Parameter Type — Numerical

 

 

⇒⇒

 

 

 

 

 

Resolution

 

 

 

 

 

 

Factory Default — 0.1

 

The parameter sets the number of decimal places to be displayed during non-

Changeable During Run — Yes

 

Accel/Decel functions.

 

 

 

 

 

 

 

 

 

 

 

⇒⇒

 

Minimum — 1

 

 

 

 

 

 

Maximum — 0.01

74

 

 

 

 

 

 

 

 

W7 ASD Installation and Operation Manual

Page 80
Image 80
Toshiba W7 manual FP Terminal Assignment, FP Terminal Adjustment, Frequency Command Panel, Frequency Display Resolution