FM Terminal Assignment |
|
|
|
|
| Frequency Display Resolution | |||
|
|
|
|
|
|
|
| ||
| FP Terminal Assignment |
|
|
|
|
|
| ||
| Program |
| Terminal Settings |
| Output Terminals | FP | FP Terminal | Parameter Type — Selection List | |
| Assignment |
|
|
|
|
| Factory Default — Output Frequency | ||
|
|
|
|
|
|
|
|
| |
| This parameter commands the multifunction programmable FP terminal to | Changeable During Run — Yes | |||||||
| monitor the value of 1 of 31 possible system functions. As the monitored | ||||||||
|
| ||||||||
| function changes in magnitude or frequency, the pulse count of the FP output |
| |||||||
| pulse train changes in direct proportion to changes in the monitored function. |
| |||||||
| As the monitored value goes up so does the pulse count of the FP output. |
| |||||||
| Note: The duty cycle of the output pulse train remains at |
|
| ||||||
| 65 ±5.0 µS. |
|
|
|
|
|
| ||
| Possible assignments for this output terminal are listed in Table 8 on page 142. |
| |||||||
|
|
|
|
|
|
|
| ||
| FP Terminal Adjustment |
|
|
|
|
|
| ||
| Program | ⇒ | Terminal Settings | ⇒ | Output Terminals | FP | FP Terminal | Parameter Type — Numerical | |
|
|
|
|
| ⇒⇒ |
|
| ||
| Adjustment |
|
|
|
|
| Factory Default — 3.840 | ||
| This parameter sets the | Changeable During Run — Yes | |||||||
| reading of the monitored variable selected in FP Terminal Setting may be set |
| |||||||
| here. | ⇒ |
| ⇒ |
|
| ⇒⇒ |
| Minimum — 1.000 |
|
|
|
|
|
| Maximum — 43.200 | |||
|
|
|
|
|
|
|
|
| Units — kHz |
| Frequency Command Panel |
|
|
|
| ||||
| Program |
| System Information and Setup | PID Setup | Frequency | Parameter Type — Numerical | |||
| Command Panel |
|
|
|
|
| Factory Default — 0.0 | ||
|
|
|
|
|
|
|
|
| |
| While operating using PID control, this parameter sets the reference frequency. | Changeable During Run — Yes | |||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| Minimum — 0.0 |
|
|
|
|
|
|
|
|
| Maximum — Max. Freq. |
|
|
|
|
|
|
|
|
| Units — Hz |
|
|
|
|
|
| ||||
| Frequency Display Resolution |
|
|
|
| ||||
| Program |
| Utilities Display Attributes | Frequency Display | Parameter Type — Numerical | ||||
|
| ⇒⇒ |
| ⇒ |
|
|
| ||
| Resolution |
|
|
|
|
|
| Factory Default — 0.1 | |
| The parameter sets the number of decimal places to be displayed during non- | Changeable During Run — Yes | |||||||
| Accel/Decel functions. |
|
|
|
|
|
| ||
|
| ⇒ |
|
|
| ⇒⇒ |
| Minimum — 1 | |
|
|
|
|
|
| Maximum — 0.01 | |||
74 |
|
|
|
|
|
|
|
| W7 ASD Installation and Operation Manual |