Base Frequency #2 |
| Base Frequency #4 | |||
|
|
| |||
Base Frequency #2 |
|
| |||
Program | Motor Settings | Base Frequency #2 | Parameter Type — Numerical | ||
The Motor #2 Base Frequency setting determines the frequency at which the | Factory Default — 60.0 | ||||
| |||||
output voltage of the ASD reaches its maximum setting. The maximum voltage | Changeable During Run — Yes | ||||
setting cannot be more that the input voltage (see the Maximum Output | |||||
| |||||
Voltage #2 parameter). There are four Base Frequency profile settings: #1 – | Minimum — 25.0 | ||||
#4. |
|
|
| Maximum — 299.0 | |
This parameter is used only when the parameters for motor set #2 are | |||||
| |||||
configured and selected. Motor set #2 may be activated via a properly | Units — Hz | ||||
configured discrete input terminal. |
| ||||
For proper motor operation, the Base Frequency should be set for the name- |
| ||||
plated frequency of the motor. |
|
| |||
|
|
| |||
Base Frequency #3 |
|
| |||
Program | Motor Settings | Base Frequency #3 | Parameter Type — Numerical | ||
The Motor #3 Base Frequency setting determines the frequency at which the | Factory Default — 60.0 | ||||
| |||||
output voltage of the ASD reaches its maximum setting. The maximum voltage | Changeable During Run — Yes | ||||
setting cannot be more that the input voltage (see the Maximum Output | |||||
| |||||
Voltage #3 parameter). There are four Base Frequency profile settings: #1 – | Minimum — 25.0 | ||||
#4. |
|
|
| Maximum — 299.0 | |
This parameter⇒is used only when⇒the parameters for motor set #3 are | |||||
| |||||
configured and selected. Motor set #3 may be activated via a properly | Units — Hz | ||||
configured discrete input terminal. |
| ||||
For proper motor operation, the Base Frequency should be set for the name- |
| ||||
plated frequency of the motor. |
|
| |||
|
|
| |||
Base Frequency #4 |
|
| |||
Program | Motor Settings | Base Frequency #4 | Parameter Type — Numerical | ||
The Motor #4 Base Frequency setting determines the frequency at which the | Factory Default — 60.0 | ||||
| |||||
output voltage of the ASD reaches its maximum setting. The maximum voltage | Changeable During Run — Yes | ||||
setting cannot be more that the input voltage (see the Maximum Output | |||||
| |||||
Voltage #4 parameter). There are four Base Frequency profile settings: #1 – | Minimum — 25.0 | ||||
#4. |
|
|
|
| |
This parameter⇒is used only when⇒the parameters for motor set #4 are | Maximum — 299.0 | ||||
configured and selected. Motor set #4 may be activated via a properly | Units — Hz | ||||
configured discrete input terminal. |
| ||||
For proper motor operation, the Base Frequency should be set for the name- |
| ||||
plated frequency⇒ | of the motor.⇒ |
|
|
W7 ASD Installation and Operation Manual | 57 |