S1 Terminal

 

 

 

S11 Terminal

 

 

 

 

S1 Terminal

 

 

 

Program

 

Terminal Settings

Input Terminals

S1 Terminal

Parameter Type — Selection List

Assignment

 

 

Factory Default — Fire Speed

 

 

 

 

 

This parameter selects the functionality of the S1 discrete input terminal.

Changeable During Run — No

 

 

 

 

 

In addition, the input terminal must be specified as Normally Open or

 

Normally Closed.

 

 

 

This parameter sets the programmable S1 terminal to 1 of the 69 possible

 

functions that are listed in Table 6 on page 138.

 

 

 

 

 

 

S10 Terminal

 

 

 

Program

 

Terminal Settings

Input Terminals

S10 Terminal

Parameter Type — Selection List

Assignment

 

 

Factory Default — Unassigned

 

 

 

 

 

This parameter selects the functionality of the S10 discrete input terminal.

Changeable During Run — No

 

 

 

 

 

Note: The S10 input terminal may be used without the ASD-

 

Multicom option board.

 

 

Without the ASD-Multicomoption board the S10 terminal

 

settings will be stored in volatile memory. The terminal

 

settings will be lost if the system is powered down or reset.

 

 

 

⇒⇒

 

 

In addition, the input terminal must be specified as Normally Open or

 

Normally Closed.

 

 

 

This parameter sets the programmable S10 terminal to 1 of the 69 possible

 

functions that are listed in Table 6 on page 138.

 

 

 

 

 

 

S11 Terminal

 

 

 

Program

 

Terminal Settings

Input Terminals

S11 Terminal

Parameter Type — Selection List

Assignment

 

 

Factory Default — Unassigned

This parameterselects the functionality⇒⇒of the S11 discrete input terminal.

Changeable During Run — No

Note: TheS11 input terminal may⇒⇒be used without the ASD-

Multicom option board.

Without the ASD-Multicomoption board the S11 terminal settings will be stored in volatile memory. The terminal settings will be lost if the system is powered down or reset.

In addition, the input terminal must be specified as Normally Open or

Normally Closed.

This parameter sets the programmable S11 terminal to 1 of the 69 possible functions that are listed in Table 6 on page 138.

W7 ASD Installation and Operation Manual

119

Page 125