82 W7 ASD Installation and Operation Manual
Low Output Disable Boost Time
Program PID Setup Low-output Disable Boost Time
The Low Output Disable Boost Time sets the on-time ti m e r for the LOD
Boost function.
Once expired, the LOD Boost function ceases.
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Delay Time
Program PID Setup Low-output Disable Delay Time
The Low Output Disable Delay Time sets the amount of time that the LOD
Start Le vel criteria must be met and mainta ined for the LOD function to be
initiated.
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Feedback Level
Program PID Setup Low-output Disable Feedback Level
The Low Output Disable Feedback Level sets a frequency level that, until the
output of the ASD drops below this setting, the Restart Delay Timer does not
start.
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Low Output Disable Restart Delay Time
Program PID Setup Low-output Disable Restart Delay
The Low Output Disable Restart Delay Time sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Selection
Program PID Setup Low-output Disable Selection
Enables/Disables the LOD function and, if enabled, selects a stopping method.
Settings:
Disabled
Enabled — Decel Stop
Enabled — Coast Stop
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Low Output Disable Boost Time Low Output Disable Selection