Torque Boost #3

 

 

Trip Save at Power Down Enable

 

 

 

 

Torque Boost #3

 

 

 

Program

 

Motor Settings

Torque Boost #3

Parameter Type — Numerical

The Motor #3 Torque Boost function is used to increase the low frequency

Factory Default — (ASD-dependent)

 

torque for high inertia loads by increasing the output voltage at frequencies

Changeable During Run — Yes

below ½ of the #3 Base Frequency setting.

 

This parameter is used only when the parameters for motor set #3 are

Minimum — 0.0

 

configured and selected. Motor set #3 may be selected by a properly configured

Maximum — 30.0

input terminal.

 

 

 

 

 

See parameter Motor #1 Torque Boost for more information on this setting.

Units — %

 

 

 

 

 

Torque Boost #4

 

 

 

Program

Motor Settings

Torque Boost #4

Parameter Type — Numerical

 

 

 

Factory Default — (ASD-dependent)

The Motor #4 Torque Boost function is used to increase the low frequency

 

torque for high inertia loads by increasing the output voltage at frequencies

Changeable During Run — Yes

below ½ of the #4 Base Frequency setting.

 

This parameter is used only when the parameters for motor set #4 are

Minimum — 0.0

configured and selected. Motor set #4 may be selected by a properly configured

Maximum — 30.0

input terminal.

 

 

 

See parameter Motor #1 Torque Boost for more information on this setting.

Units — %

 

Torque Reference

Address

 

Program

 

Communication Settings Torque Reference Address

Parameter Type — Selection List

The S20 system is Toshiba’s high-speed fiber optic communication system.

Factory Default — 0

 

This function is unavailable at the time of this release.

 

 

 

Torque Reference Station

 

Program

 

Communication Settings Torque Reference Station

Parameter Type — Selection List

The S20 system is Toshiba’s high-speed fiber optic communication system.

Factory Default — 0

 

This function is unavailable at the time of this release.

Transmit Address

Program Communication Settings Transmit Address

The S20 system is Toshiba’s high-speed fiber optic communication system. This function is unavailable at the time of this release.

Parameter Type — Selection List Factory Default — 0

Trip Save at Power Down Enable

Program Protection Settings Trip Save at Power Down

This parameter Enables/Disables theTrip Save at Power Down setting. When enabled, this feature logs the trip event and retains the trip information when the system powers down. The trip information may be viewed from the Monitor screen.

When disabled, the trip information will be cleared when the system powers down.

130

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

W7 ASD Installation and Operation Manual