Toshiba W7 OUT7 On Delay, OUT7 Terminal, Output Phase Loss Detection, Output Short Circuit Test

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 98
Image 98

OUT7 On Delay

 

 

 

Output Short Circuit Test Duration

 

 

 

 

 

OUT7 On Delay

 

 

 

 

Program

Terminal Settings

Terminal Delays

 

Output Terminal

Parameter Type — Numerical

Delays

 

⇒⇒

 

 

OUT7 On Delay

 

 

 

Factory Default — 2.0

This parameter delays the response of the OUT7 output contacts by the

Changeable During Run — No

programmed value (see waveforms at FL On Delay).

 

 

 

The delay may be increased to prevent relay chatter.

 

 

Minimum — 2.0

 

 

 

 

 

 

Maximum — 200.0

 

 

 

 

 

 

Units — mS

OUT7 Terminal

 

 

 

 

Program

 

Terminal Settings

Output Terminals

 

OUT7 Terminal

Parameter Type — Selection List

Assignment

 

 

 

Factory Default — OC Alarm

 

 

 

 

 

 

This parameter sets the functionality of the OUT7 output contacts to 1 of the 58

Changeable During Run — No

possible functions that are listed in Table 7 on page 141.

 

 

 

The on and off delay times of the OUT7 contacts may be adjusted to provide

 

more response time to the device that is connected to the output terminals.

 

In addition, the output contacts must be specified as Normally Open or

 

Normally Closed.

 

 

 

 

 

 

 

 

Output Phase Loss Detection

 

 

 

Program

Protection Settings Output Phase Loss Detection

Parameter Type — Selection List

This parameter Enables/Disables the monitoring of each phase of the 3-phase

Factory Default — Disabled

 

output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not

Changeable During Run — No

of the specified level, the ASD incurs a trip.

 

 

 

 

 

 

 

 

 

 

Output Short Circuit Test

 

 

 

 

Program Protection Settings Output Short Circuit Test

Parameter Type — Selection List

This parameter determines when the system will perform an Output Short

Factory Default — Standard

 

Circuit test.

 

Changeable During Run — No

 

 

 

 

 

 

Settings:

First Time (each startup from off or reset)

Standard (each startup)

Output Short Circuit Test Duration

Program

Protection Settings

Output Short Circuit Test Duration

92

This parameter sets the pulse width of the ASD output pulse that is applied to the motor during an Output Short Circuit test.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — No

Minimum — 1

Maximum — 100

Units — µS

W7 ASD Installation and Operation Manual

Page 98
Image 98
Toshiba W7 manual OUT7 On Delay, OUT7 Terminal, Output Phase Loss Detection, Output Short Circuit Test