OUT7 On Delay |
|
|
| Output Short Circuit Test Duration | ||
|
|
|
|
| ||
OUT7 On Delay |
|
|
|
| ||
Program | ⇒ | Terminal Settings | Terminal Delays |
| Output Terminal | Parameter Type — Numerical |
Delays |
| ⇒⇒ |
|
| ||
OUT7 On Delay |
|
|
| Factory Default — 2.0 | ||
This parameter delays the response of the OUT7 output contacts by the | Changeable During Run — No | |||||
programmed value (see waveforms at FL On Delay). |
|
|
| |||
The delay may be increased to prevent relay chatter. |
|
| Minimum — 2.0 | |||
|
|
|
|
|
| Maximum — 200.0 |
|
|
|
|
|
| Units — mS |
OUT7 Terminal |
|
|
|
| ||
Program |
| Terminal Settings | Output Terminals |
| OUT7 Terminal | Parameter Type — Selection List |
Assignment |
|
|
| Factory Default — OC Alarm | ||
|
|
|
|
|
| |
This parameter sets the functionality of the OUT7 output contacts to 1 of the 58 | Changeable During Run — No | |||||
possible functions that are listed in Table 7 on page 141. |
| |||||
|
| |||||
The on and off delay times of the OUT7 contacts may be adjusted to provide |
| |||||
more response time to the device that is connected to the output terminals. |
| |||||
In addition, the output contacts must be specified as Normally Open or |
| |||||
Normally Closed. |
|
|
|
| ||
|
|
|
| |||
Output Phase Loss Detection |
|
|
| |||
Program⇒ | Protection Settings Output Phase Loss Detection | Parameter Type — Selection List | ||||
This parameter Enables/Disables the monitoring of each phase of the | Factory Default — Disabled | |||||
| ||||||
output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not | Changeable During Run — No | |||||
of the specified level, the ASD incurs a trip. |
|
| ||||
|
|
| ||||
|
|
|
|
| ||
Output Short Circuit Test |
|
|
|
| ||
Program ⇒Protection Settings ⇒Output Short Circuit Test | Parameter Type — Selection List | |||||
This parameter determines when the system will perform an Output Short | Factory Default — Standard | |||||
| ||||||
Circuit test.⇒ |
| ⇒ | ⇒ | Changeable During Run — No | ||
|
|
|
|
|
|
Settings:
First Time (each startup from off or reset)
Standard (each startup)
Output Short Circuit Test Duration
Program | Protection Settings | Output Short Circuit Test Duration |
92 | ⇒ | ⇒ |
This parameter sets the pulse width of the ASD output pulse that is applied to the motor during an Output Short Circuit test.
Parameter Type — Numerical
Factory Default —
Changeable During Run — No
Minimum — 1
Maximum — 100
Units — µS
W7 ASD Installation and Operation Manual