RX2 Speed Frequency Setpoint #1

RX2 Speed Frequency Setpoint #2

RX2 Speed Frequency Setpoint #1

Program Frequency Settings Speed Reference Setpoints RX2

Perform thefollowing setup to allowthe system to perform Speed controlfrom the RX2 input terminal:

RX2 Speed Frequency Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX2 input terminal when the RX2 terminal is used as the control input while operating in the Speed Control mode.

Note: The RX2 input terminal is available with the ASD-Multicom

option board only.

RX2 Input Speed/Direction Control Setup

Perform the following setup to allow the system to receive Speed control input at the RX2 input terminal:

Program Utilities

Command and Frequency Settings Command

 

Mode Select Terminal Block.

Program Utilities Command and Frequency Settings Frequency#1

 

Mode Select RX.

 

Provide a Run command (F and/or R).

Speed/Direction Control

Set RX2 Speed Frequency #1,

Set the RX2 input signal level (RX2 Speed Ref #1) that represents RX2 Speed Frequency #1,

Set RX2 Speed Frequency Setpoint #2, and

Set the RX2 input signal level (RX2 Speed Ref #2) that represents RX2 Speed Frequency Setpoint #2.

Once set, as the RX2 input voltage changes, the directional information, and the output frequency of the ASD will vary in accordance with the above settings.

This parameter sets RX2 Speed Frequency #1 and is the frequency that is associated with the setting of RX2 Speed Reference #1 when operating in the Speed Control mode.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

Frequency Settings

RX2 Speed Frequency Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

RX2

RX2 Speed Frequency Setpoint #2

 

This parameter is used to set the direction, gain, and bias of the RX2 input terminal when the RX2 terminal is used as the control input while operating in the Speed Control mode.

See RX2 Speed Frequency Setpoint #1 for further information on this setting.

This parameter sets RX2 Speed Frequency #2 and is the frequency that is associated with the setting of RX2 Speed Reference #2 when operating in the Speed Control mode.

W7 ASD Installation and Operation Manual

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

113

Page 119
Image 119