RR Speed Reference Setpoint #1 |
|
| RR Speed Reference Setpoint #2 | ||
|
|
| |||
RR Speed Reference Setpoint #1 |
|
| |||
Program | Frequency Settings | RR | RR Speed Reference | Parameter Type — Numerical | |
Setpoint #1 |
|
| Factory Default — 0.00 | ||
|
|
|
| ||
This parameter is used to set the gain and bias of the RR input terminal when | Changeable During Run — Yes | ||||
the RR terminal is used as the control input while operating in the Speed | |||||
| |||||
Control or the Torque Control mode. |
|
| Minimum — 0.0 | ||
See RR Speed Frequency #1 for further information on this setting when used | Maximum — 100.0 | ||||
for Speed control. |
|
| Units — % | ||
See RR Torque Reference #1 for further information on this setting when used | |||||
| |||||
for Torque control. |
|
|
| ||
This parameter sets the RR input level that is associated with RR Speed |
| ||||
Frequency #1 when operating in the Speed control mode or is associated with |
| ||||
the RR Torque Reference #1 when operating in the Torque control mode. |
| ||||
This value is entered as 0.0 to +100% of the 0 – 10 VDC RR input signal range. |
| ||||
|
|
| |||
RR Speed Reference Setpoint #2 |
|
| |||
Program | Frequency Settings | RR | RR Speed Reference | Parameter Type — Numerical | |
Setpoint #2 |
|
| Factory Default — 0.00 | ||
|
|
|
| ||
This parameter is used to set the gain and bias of the RR input terminal when | Changeable During Run — Yes | ||||
the RR terminal⇒is used as the control⇒⇒input while operating in the Speed | |||||
| |||||
Control or the Torque Control mode. |
|
| Minimum — 0.0 | ||
See RR Speed Frequency #1 for further information on this setting when used | Maximum — 100.0 | ||||
for Speed control. |
|
|
|
⇒⇒⇒ Units — % See RR Torque Reference #1 for further information on this setting when used
for Torque control.
This parameter sets the RR input level that is associated with RR Speed Frequency #2 when operating in the Speed control mode or is associated with the RR Torque Reference #2 when operating in the Torque control mode.
This value is entered as 0.0 to +100% of the 0 – 10 VDC RR input signal range.
108 | W7 ASD Installation and Operation Manual |