BIN Speed Reference Setpoint #1

 

 

BIN Torque Reference Reference #2

 

 

 

BIN Speed Reference Setpoint #1

 

 

Program

Frequency Settings

Speed Reference Setpoints

BIN

Parameter Type — Numerical

BIN Speed Reference Setpoint #1

 

Factory Default — 0.00

 

 

 

 

This parameter is used to set the direction, gain, and bias of the discrete input

Changeable During Run — Yes

terminals when using the discrete input terminals as the control input while

 

operating in the Speed Control or the Torque Control mode.

 

Minimum — 0.00

See BIN Speed Frequency Setpoint #1 for further information on this setting

Maximum — 100.00

when used for Speed control.

 

 

 

 

 

See BIN Torque Reference Reference #1 for further information on this

Units — %

 

setting when used for Torque control.

 

 

 

This parameter sets the BIN input that is associated with BIN Speed

 

 

Frequency #1 when operating in the Speed control mode or is associated with

 

the BIN Torque Reference #1 when operating in the Torque control mode.

 

This value is entered as 0 to 100% of the binary input word 11111111 (255D).

 

 

 

 

BIN Speed Reference Reference #2

 

 

Program

Frequency Settings

Speed Reference Setpoints

BIN

Parameter Type — Numerical

BIN Speed Reference Setpoint #2

 

Factory Default — 100.00

 

 

 

 

This parameter is used to set the direction, gain, and bias of the discrete input

Changeable During Run — Yes

terminals whenusing the discrete inputterminals as the control input ⇒⇒while

 

operating in the Speed Control or the Torque Control mode.

 

Minimum — 0.00

See BIN Speed Frequency Setpoint #1 for further information on this setting

Maximum — 100.0

when used for Speed control.

 

See BIN Torque Reference Reference #1 for further information on this

Units — %

 

setting when used for Torque control.

 

This parameter sets the BIN input that is associated with BIN Speed

 

Frequency #2 when operating in the Speed control mode or is associated with

 

the BIN Torque Reference #2 when operating in the Torque control mode.

 

This valueis entered as 0 to 100% ofthe binary input word 11111111⇒⇒(255D).

 