RX2 Torque Reference Setpoint #1

RX2 Torque Reference Setpoint #2

RX2 Torque Reference Setpoint #1

Program Frequency Settings Speed Reference Setpoints RX2

RX2 Torque Reference Setpoint #1

Torque Reference #1,

This parameter is used to set the direction, gain, and bias of the RX2 input terminal when the RX2 terminal is used as the control input while operating in the Torque Control mode.

RX2 Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input at the RX2 input terminal:

Program Utilities Command and Frequency Settings Command

 

Mode Select Terminal Block.

Program Utilities Command and Frequency Settings Frequency#1

 

Mode Select RX2.

Provide a Run command (F and/or R).

Torque Control

Perform the following setup to allow the system to perform Torque control from the RX2 input terminal:

Set RX2 Torque Reference #1,

Set the RX2input signal level (RX2Speed Ref #1) that represents theRX2

Set RX2 Torque Reference Setpoint #2, and

Set the RX2 input signal level (RX2 Speed Ref #2) that represents the RX2 Torque Reference Setpoint #2.

This is accomplished by establishing an associated V/f output pattern for a given RX2 input level.

This parameter sets RX2 Torque Reference #1 and is the output torque value that is associated with the setting of RX2 Speed Reference Setpoint #1 when operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

Torque Settings

RX2 Torque Reference Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

RX2

RX2 Torque Reference Setpoint #2

 

This parameter is used to set the direction, gain, and bias of the RX2 input terminal when the RX2 terminal is used as the control input while operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given RX2 input level.

See RX2 Torque Reference Setpoint #1 for further information on this setting.

This parameter sets RX2 Torque Reference #2 and is the output torque value that is associated with setting of RX2 Speed Reference Setpoint #2 when operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

W7 ASD Installation and Operation Manual

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

115

Page 121