Electronic Thermal Protection #1

 

Electronic Thermal Protection #4

 

 

 

Electronic Thermal Protection #1

 

 

Program

 

Motor Settings Electronic Thermal Protection #1

Parameter Type — Numerical

This parameter specifies the motor overload current level for motor set #1. This

Factory Default — 100.0

 

value is entered as either a percentage of the full load rating of the ASD or as

Changeable During Run — Yes

the FLA of the motor.

 

 

 

 

 

The unit of measurement for this parameter may be set to Amps or it may be set

Minimum — 10.0

 

as a percentage of the ASD rating. The name-plated FLA of the motor may be

Maximum — 100.0

entered directly when Amps is selected as the unit of measurement (see

 

Program

 

Utilities

Display Attributes

Units for V/I to change the

Units — %

display unit).

 

 

 

 

 

Thermal Protection settings will be displayed in Amps if the keypad display

 

units are set to V/I rather than %.

 

 

 

 

 

Electronic Thermal Protection #2

 

 

Program

 

Motor Settings Electronic Thermal Protection #2

Parameter Type — Numerical

This parameter specifies the motor overload current level for motor set #2. This

Factory Default — 100.0

 

value is entered as either a percentage of the full load rating of the ASD or as

Changeable During Run — Yes

the FLA of the motor.

 

 

 

 

 

The unit of measurement for this parameter may be set to Amps or it may be set

Minimum — 10.0

 

as a percentage of the ASD rating. The name-plated FLA of the motor may be

Maximum — 100.0

entered directlywhen Amps isselected as the unit of measurement (see

 

Program

 

Utilities

Display Attributes

Units for V/I to change the

Units — %

display unit).

 

 

 

 

 

Thermal Protection settings will be displayed in Amps if the keypad display

 

units are set to V/I rather than %.

 

 

 

 

 

Electronic Thermal Protection #3

 

 

Program

 

Motor Settings Electronic Thermal Protection #3

Parameter Type — Numerical

 

 

⇒⇒

 

This parameter specifies the motor overload current level for motor set #3. This

Factory Default — 100.0

 

value is entered as either a percentage of the full load rating of the ASD or as

Changeable During Run — Yes

the FLA of the motor.

 

 

 

 

 

The unit of measurement for this parameter may be set to Amps or it may be set

Minimum — 10.0

 

as a percentage of the ASD rating. The name-plated FLA of the motor may be

 

entered directly

when Amps isselected as the unit of measurement (see

Maximum — 100.0

Program

 

Utilities

Display Attributes

Units for V/I to change the

Units — %

display unit).

 

 

 

 

 

Thermal Protection settings will be displayed in Amps if the keypad display

 

units are set to V/I rather than %.

 

 

 

 

 

Electronic Thermal Protection #4

 

 

Program

 

Motor Settings Electronic Thermal Protection #4

Parameter Type — Numerical

 

 

⇒⇒

 

This parameter specifies the motor overload current level for motor set #4. This

Factory Default — 100.0

value is entered as either a percentage of the full load rating of the ASD or as

Changeable During Run — Yes

the FLA of the motor.

 

 

The unit of measurement for this parameter may be set to Amps or it may be set

Minimum — 10.0

as a percentage of the ASD rating. The name-plated FLA of the motor may be

 

entered directly

when Amps isselected as the unit of measurement (see

Maximum — 100.0

Program

 

Utilities

Display Attributes

Units for V/I to change the

Units — %

display unit).

 

 

 

 

 

 

 

 

 

Thermal Protection settings will be displayed in Amps if the keypad display

 

70units are set⇒⇒to V/I rather⇒⇒than%.

 

W7 ASD Installation and Operation Manual

Page 76
Image 76