RX Speed Frequency Setpoint #1

RX Speed Frequency Setpoint #2

RX Speed Frequency Setpoint #1

Program Frequency Settings Speed Reference Setpoints RX

Speed Frequency Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX input terminal when the RX terminal is used as the control input while operating in the Speed Control mode.

RX Input Speed/Direction Control Setup

Perform the following setup to allow the system to receive Speed control input at the RX input terminal:

Program Utilities

Command and Frequency Settings Command

 

Mode Select Terminal Block.

Program Utilities Command and Frequency Settings Frequency#1

 

Mode Select RX.

 

Provide a Run command (F and/or R).

Speed/Direction Control

Perform the following setup to allow the system to perform Speed control from the RX input terminal:

Set RX Speed Frequency #1,

Set the RXinput signal level (RXSpeed Ref #1) that represents RXSpeed

 

Frequency #1,

Set RX Speed Frequency Setpoint #2, and

Set the RX input signal level (RX Speed Ref #2) that represents RX Speed

 

Frequency Setpoint #2.

Once set, as the RX input voltage changes, the directional information, and the output frequency of the ASD will vary in accordance with the above settings.

This parameter sets RX Speed Frequency #1 and is the frequency that is associated with the setting of RX Speed Reference Setpoint #1 when operating in the Speed Control mode.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

Frequency Settings

RX Speed Frequency Setpoint #2

Program Frequency Settings Speed Reference Setpoints RX

Speed Frequency Setpoint #2

This parameteris used to set the direction,gain, and bias of the RX inputterminal when the RX terminal is used as the control input while operating in the Speed Control mode.

See RX Speed Frequency Setpoint #1 for further information on this setting.

This parameter sets RX Speed Frequency Setpoint #2 and is the frequency that is associated with the setting of RX Speed Reference Setpoint #2 when operating in the Speed Control mode.

116

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

W7 ASD Installation and Operation Manual

Page 122
Image 122
Toshiba W7 manual RX Speed Frequency Setpoint #1, RX Speed Frequency Setpoint #2, RX Input Speed/Direction Control Setup