Toshiba W7 manual VI/II Speed Frequency Setpoint #2, VI/II Speed Reference Setpoint #1

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 141
Image 141

VI/II Speed Frequency Setpoint #2

 

VI/II Speed Reference Setpoint #2

 

 

 

VI/II Speed Frequency Setpoint #2

 

 

Program

Frequency Settings

Speed Reference Setpoints

VI/II

Parameter Type — Numerical

VI/II Speed Frequency Setpoint #2

 

Factory Default — 80.0

 

 

 

 

 

 

This parameter is used to set the gain and bias of the VI/II input terminal when

Changeable During Run — Yes

the VI/II terminal is used as the control input while operating in the Speed

 

Control mode.

 

 

 

Minimum — 0.0

See VI/II Speed Frequency Setpoint #1 for further information on this setting.

Maximum — Max. Freq.

 

 

 

 

 

 

This parameter sets VI/II Speed Frequency Setpoint #2 and is the frequency

Units — Hz

that is associated with the setting of VI/II Speed Reference Setpoint #2 when

 

operating in the Speed Control mode.

 

 

 

 

 

VI/II Speed Reference Setpoint #1

 

 

Program

Frequency Settings

Speed Reference Setpoints

VI/II

Parameter Type — Numerical

 

 

 

 

VI/II Speed Reference Setpoint #1

 

Factory Default — 20.00

 

 

 

 

 

This parameter is used to set the gain and bias of the VI/II input terminal when

Changeable During Run — Yes

the VI/II terminal is used as the control input while operating in the Speed

 

Control or the Torque Control mode.

 

Minimum — 0.0

See VI/II Speed Frequency Setpoint #1 for further information on this setting

Maximum — 100.0

when used for Speed control.

 

 

 

See VI/II Torque

Reference Setpoint#1 for further information on thissetting

Units — %

when

used for Torque control.

 

 

 

This parameter sets the VI/II input level that is associated with VI/II Speed

 

Frequency Setpoint #1 when operating in the Speed control mode or is

 

associated with the VI/II Torque Reference Setpoint #1 when operating in the

 

Torque control mode.

 

 

 

This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal

 

range.

 

 

 

 

 

The default value for this parameter is 20%. The II input is commonly used for

 

the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal.

 

If the VI input is used (0 – 10 VDC input), this parameter may be changed to

 

0.0% (of the input signal).

 

 

 

 

 

 

VI/II Speed Reference Setpoint #2

 

 

Program

Frequency Settings

Speed Reference Setpoints

VI/II

Parameter Type — Numerical

VI/II Speed Reference Setpoint #2

 

Factory Default — 0.00

 

 

 

 

 

 

 

 

 

 

 

This parameter is used to set the gain and bias of the VI/II input terminal when

Changeable During Run — Yes

the VI/II terminal is used as the control input while operating in the Speed

 

Control or the Torque Control mode.

 

Minimum — 0.0

See VI/II Speed Frequency Setpoint #1 for further information on this setting

Maximum — 100.0

when used for Speed control.

 

 

 

 

 

See VI/II Torque Reference Setpoint #1 for further information on this setting

Units — %

 

when used for Torque control.

 

 

 

This parameter sets the VI/II input level that is associated with VI/II Speed

 

Frequency Setpoint #2 when operating in the Speed control mode or is

 

associated with the VI/II Torque Reference Setpoint #2 when operating in the

 

Torque control mode.

 

 

 

This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal

 

range.

 

and Operation Manual

 

W7 ASD Installation

135

Page 141
Image 141
Toshiba W7 manual VI/II Speed Frequency Setpoint #2, VI/II Speed Reference Setpoint #1, VI/II Speed Reference Setpoint #2