VI/II Speed Frequency Setpoint #2 |
| VI/II Speed Reference Setpoint #2 | |||||
|
|
| |||||
VI/II Speed Frequency Setpoint #2 |
|
| |||||
Program | Frequency Settings | Speed Reference Setpoints | VI/II | Parameter Type — Numerical | |||
VI/II Speed Frequency Setpoint #2 |
| Factory Default — 80.0 | |||||
|
|
|
|
|
| ||
This parameter is used to set the gain and bias of the VI/II input terminal when | Changeable During Run — Yes | ||||||
the VI/II terminal is used as the control input while operating in the Speed | |||||||
| |||||||
Control mode. |
|
|
| Minimum — 0.0 | |||
See VI/II Speed Frequency Setpoint #1 for further information on this setting. | Maximum — Max. Freq. | ||||||
|
|
|
|
|
| ||
This parameter sets VI/II Speed Frequency Setpoint #2 and is the frequency | Units — Hz | ||||||
that is associated with the setting of VI/II Speed Reference Setpoint #2 when | |||||||
| |||||||
operating in the Speed Control mode. |
|
| |||||
|
|
| |||||
VI/II Speed Reference Setpoint #1 |
|
| |||||
Program | Frequency Settings | Speed Reference Setpoints | VI/II | Parameter Type — Numerical | |||
|
| ⇒ |
| ⇒ | ⇒ |
| |
VI/II Speed Reference Setpoint #1 |
| Factory Default — 20.00 | |||||
⇒ |
|
|
|
|
| ||
This parameter is used to set the gain and bias of the VI/II input terminal when | Changeable During Run — Yes | ||||||
the VI/II terminal is used as the control input while operating in the Speed |
| ||||||
Control or the Torque Control mode. |
| Minimum — 0.0 | |||||
See VI/II Speed Frequency Setpoint #1 for further information on this setting | Maximum — 100.0 | ||||||
when used for Speed control. |
|
|
| ||||
See VI/II Torque⇒ | Reference Setpoint⇒#1 for further information on this⇒setting | Units — % | |||||
when⇒ | used for Torque control. |
|
|
| |||
This parameter sets the VI/II input level that is associated with VI/II Speed |
| ||||||
Frequency Setpoint #1 when operating in the Speed control mode or is |
| ||||||
associated with the VI/II Torque Reference Setpoint #1 when operating in the |
| ||||||
Torque control mode. |
|
|
| ||||
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal |
| ||||||
range. |
|
|
|
|
| ||
The default value for this parameter is 20%. The II input is commonly used for |
| ||||||
the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal. |
| ||||||
If the VI input is used (0 – 10 VDC input), this parameter may be changed to |
| ||||||
0.0% (of the input signal). |
|
|
| ||||
|
|
| |||||
VI/II Speed Reference Setpoint #2 |
|
| |||||
Program | Frequency Settings | Speed Reference Setpoints | VI/II | Parameter Type — Numerical | |||
VI/II Speed Reference Setpoint #2 |
| Factory Default — 0.00 | |||||
⇒ |
|
|
|
|
| ||
|
|
|
|
|
| ||
This parameter is used to set the gain and bias of the VI/II input terminal when | Changeable During Run — Yes | ||||||
the VI/II terminal is used as the control input while operating in the Speed | |||||||
| |||||||
Control or the Torque Control mode. |
| Minimum — 0.0 | |||||
See VI/II Speed Frequency Setpoint #1 for further information on this setting | Maximum — 100.0 | ||||||
when used for Speed control. |
|
| |||||
|
|
| |||||
See VI/II Torque Reference Setpoint #1 for further information on this setting | Units — % | ||||||
| |||||||
when used for Torque control. |
|
|
| ||||
This parameter sets the VI/II input level that is associated with VI/II Speed |
| ||||||
Frequency Setpoint #2 when operating in the Speed control mode or is |
| ||||||
associated with the VI/II Torque Reference Setpoint #2 when operating in the |
| ||||||
Torque control mode. |
|
|
| ||||
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal |
| ||||||
range. |
| and Operation Manual⇒ | ⇒ |
| |||