Communications Reference Setpoint #1 | Communications Reference Selection |
Communications Reference Setpoint #1
Program Communications Settings | Communication Reference |
⇒ | ⇒ |
Setpoint #1 |
|
When enabled via the Communications Reference Select parameter, this parameter is used to allow the user to set the gain and bias of the speed control input to the ASD when the speed control signal is received via the source selected at the Communications Reference Select parameter.
Gain and Bias Settings
When operating in the Speed Control mode and using one of the control sources from the Communications Reference Select parameter, the settings that determine the gain and bias properties of the input signal are:
• Communications Speed #1 (Hz),
• the communications input signal value that represents Communications Speed #1 (Hz),
• Communications Speed #2 (Hz), and
• the communications input signal value that represents Communications Speed #2 (Hz).
Once set, as the input signal value changes, the output frequency of the ASD will vary in accordance with the above settings.
This parameter sets the Communications Reference input value that represents Communications Speed #1. This value is entered as 0 to 100% of the Communications Reference input value range.
Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Frequency Settings
Communications Reference Setpoint #2
Program | Communications Settings |
| Comm Reference Setpoint #2 | Parameter Type — Numerical | |||
This parameter is used to set the gain and bias of the Communications | Factory Default — 100.0 | ||||||
| |||||||
Reference speed control input. |
|
| Changeable During Run — Yes | ||||
|
|
|
|
|
| ||
See Communications Reference Setpoint #1 for further information on this | Minimum — 0.00 | ||||||
setting. |
|
|
|
|
| ||
|
|
|
|
|
| ||
This parameter sets the Communications Reference input value that represents | Maximum — 100.0 | ||||||
Communications Speed #2 (Hz). This value is entered as 0 to 100% of the | Units — % | ||||||
Communications Reference input value range. | |||||||
| |||||||
Changes made to this parameter require that the power be cycled (Off then On) |
| ||||||
for the changes to take effect. |
|
|
| ||||
|
| ||||||
Communications Reference Selection |
| ||||||
Program | Communications Settings |
| Communications Reference | Parameter Type — Selection List | |||
Selection |
|
|
|
|
| Factory Default — Disabled | |
|
|
|
|
|
| ||
This parameter Enable/Disables speed control via communications. Selecting a | Changeable During Run — Yes | ||||||
signal source enables this function. Selecting Disable disables this function. | |||||||
| |||||||
Settings: |
|
|
| ⇒ |
|
| |
Communications⇒ | Card |
|
| ||||
RS232/RS485 |
|
| ⇒ |
|
| ||
LCD Keypad |
|
|
|
| |||
Disabled |
|
|
|
|
| ||
W7 ASD Installation⇒ | and Operation Manual |
| 63 |