RR Speed Frequency Setpoint #1

 

 

RR Speed Frequency Setpoint #2

RR Speed Frequency Setpoint #1

 

 

Program

Frequency Settings

RR

RR Speed Frequency

Parameter Type — Numerical

Setpoint #1

 

 

 

 

Factory Default — 0.0

 

 

 

 

 

 

 

This parameter is used to set the gain and bias of the RR input terminal when

Changeable During Run — Yes

the RR terminal is used as the control input while operating in the Speed

 

Control mode.

 

 

 

 

Minimum — 0.0

RR Input Speed Control Setup

 

 

Maximum — 80.0

Perform the following setup to allow the system to receive Speed control input

Units — Hz

at the RR input terminal:

 

 

 

 

Program

Utilitites

Command and Frequency Settings Frequency

 

 

Mode#1 Select

RR.

 

 

 

• Program Utilitites Command and Frequency Settings Command

Frequency Settings

 

Mode Select

(any setting).

 

 

 

Provide a Run command (F and/or R).

 

 

Speed Control

 

 

 

 

 

Perform the following setup to allow the system to perform Speed control from

 

the RR input terminal:

 

 

 

 

Set RR Speed Frequency #1,

 

 

 

Set the RRinput signal level (RR⇒⇒Speed Ref #1) that represents RR Speed

 

 

Frequency #1,

 

 

 

 

 

Set RR Speed Frequency #2, and

 

 

 

Set the RR input signal level (RR Speed Ref #2) that represents RR Speed

 

 

Frequency #2.

 

 

 

 

 

Once set, as the RR input voltage changes the output frequency of the ASD will

 

vary in accordance with the above settings.

 

 

This parameter sets RR Speed Frequency #1 and is the frequency that is

 

associated with the setting of RR Speed Reference #1 when operating in the

 

Speed Control mode.

 

 

 

 

RR Speed Frequency Setpoint #2

 

 

Program

Frequency

Settings

RR

RR Speed Frequency

Parameter Type — Numerical

Setpoint #2

 

 

 

 

Factory Default — 80.0

 

 

 

 

 

 

 

This parameter is used to set the gain and bias of the RR input terminal when

Changeable During Run — Yes

the RR terminal is used as the control input while operating in the Speed

 

Control mode.

 

 

 

 

Minimum — 0.0

See RR Speed Frequency #1 for further information on this setting.

Maximum — 80.0

This parameter sets RR Speed Frequency #2 and is the frequency that is

Units — Hz

associated with the setting of RR Speed Reference #2 when operating in the

 

W7SpeedASD ControlInstallationmode.and Operation Manual⇒⇒

 

107

Page 113
Image 113
Toshiba W7 manual RR Speed Frequency Setpoint #1, RR Speed Frequency Setpoint #2, RR Input Speed Control Setup