Mitsubishi Electronics MXZ-32SV service manual Check of thermistor

Models: MXZ-32SV

1 44
Download 44 pages 62.89 Kb
Page 32
Image 32

• When thermistor is abnormal. (When the LED display is a table below.)

F Check of thermistor

Start

 

 

Abnormal

 

 

Disconnect the connector in the electronic control P. C. board (see below table), and

measure the resistance of thermistor to check whether the thermistor is normal or not.

 

 

Normal

 

 

 

Replace the thermistor

Reconnect the connector (CN661, CN662 and CN663) and disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.

Does thermistor operate 10 minutes or more though the No thermistor abnormality is not displayed?

Yes

Normal

Replace the electronic control P. C. board.

Thermistor

Symbol

Connector, Pin No.

Defrost thermistor

RT62

Between CN661 pin1 and pin2

Discharge temperature thermistor

RT61

Between CN661 pin3 and pin4

Evaporation temperature thermistor

RT63

Between CN661 pin5 and pin6

Gas pipe temperature thermistor (Unit A)

RT66

Between CN662 pin1 and pin2

Gas pipe temperature thermistor (Unit B)

RT67

Between CN662 pin3 and pin4

Gas pipe temperature thermistor (Unit C)

RT68

Between CN662 pin5 and pin6

Gas pipe temperature thermistor (Unit D)

RT69

Between CN662 pin7 and pin8

Fin temperature thermistor

RT65

Between CN663 pin1 and pin2

• Fan motor does not operate. Or, fan motor stops at once’ after fan motor operates.

G Check of fan motor

Start

Check the connection of connector (CN851, CN852) in the fan motor relay connector and electronic control P. C. board at the noise filter P. C. board and connector (CN901, CN902) in the noise filter board.

Disconnect the fan motor connector, and measure the resistance of the

Abnormal

 

Replace the fan motor

fan motor winding to check the winding characteristic.

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

1.Disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.

2.Check the voltage between pin 2 and pin 3, pin 2 and pin 5, pin 2 and pin 6 at the fan motor connector.

Is there voltage of 220V AC - 240V AC? No

Yes

1.

Turn off power supply of the indoor and outdoor unit, and disconnect the connector

 

 

 

No

Replace the electronic

 

(CN851, CN852).

 

 

 

control P. C. board

2.

Is the voltage 0V, when the voltage between CN852 pin1 (+) and CN851 pin1 (-),

 

 

 

 

 

pin2 (-), or pin3 (-) are measured after the power supply is turned on the outdoor unit?

 

Yes

 

Is there voltage of 12V DC between CN852 pin1 (+) and pin3 (-), when power supply

No

turns on the indoor unit and EMERGENCY OPERATION starts in three minutes.

 

 

Yes

 

 

 

 

 

Replace the noise filter P. C. board

 

 

32