Mitsubishi Electronics MXZ-32SV service manual Check of LEV

Models: MXZ-32SV

1 44
Download 44 pages 62.89 Kb
Page 31
Image 31

When cooling, heat exchanger of non-operating indoor unit frosts.

When heating, non-operating indoor unit get warm.

(LED display: 00, p1)

D Check of LEV

Start

Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.

Is "click - click" sound heard?

Or, do you feel vibration of the LEV coil with a hand?

No

Disconnect the connector

(CN791: unit A, CN792: unit B, CN793: unit C,

CN794: unit D), and measure the resistance of LEV coil to check the integrity.

No

Replace the LEV coil.

Yes

Nomal

Yes Replace the electronic control P. C. board

When heating, room does not get warm.

When cooling, room does not get cool. (LED display: 00, a8)

E Check of inverter/ compressor

Start

Disconnect the lead wire to the compressor at terminals, and turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.

 

 

 

W1 • After the outdoor fan starts running, wait for 1 minutes or more before

 

 

 

Measure the voltage between

 

measuring the voltage.

 

 

 

 

each leading to the compressor.

• The output voltage values in the above table have the tolerance of i20%.

U (BLK) - V (WHT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V (WHT) - W (RED)

 

No

LED indicator the inverter

No

 

1. Turn off power supply of the indoor

W (RED) - U (BLK)

 

 

 

 

stops due to over current?

 

 

and outdoor unit, and disconnect

Output voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the connector CN 551 in the relay

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL: 100V(58Hz) HEAT: 100V(58Hz)

 

 

 

 

 

 

 

 

Yes

 

 

P. C. board

Is voltage output? W1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Turn on power supply to the outdoor

 

 

 

 

 

Replace the electronic

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

unit, and after 1 minutes or more

 

 

 

 

 

 

 

 

 

 

 

 

 

control P. C. board

 

 

 

 

Is output balanced?

No

 

 

 

 

 

 

 

 

passed, check the resistance

 

 

 

 

with the I.P.M P. C. board.

 

 

 

 

 

 

 

 

 

 

 

 

between the connector

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN551 pin 1 and pin 2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn off power supply of indoor and outdoor unit,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and measure the compressor winding resistance

 

No

 

 

 

0"

 

Check the resistance

between the compressor terminals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between each terminal

Is there resistance of 0.27" to 0.34" between

 

 

 

 

 

 

 

 

 

 

the each terminals?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Infinite

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

compressor.

 

 

 

After 1 minutes has passed since the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return the lead wire of compressor to former, and

 

 

 

 

 

 

 

 

 

 

power supply of outdoor unit was

 

 

 

 

 

 

 

 

 

 

turned off, disconnect the connector

turn on power supply to indoor and outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN 553 in the noise filter P. C. board.

Three minutes later EMERGENCY OPERATION starts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short

10 to 60 seconds: compressor lock

60 seconds to 5minutes: refrigerant circuit defective

5 minutes or more: normal

0"

Replace the relay P. C. board.

Check the resistance HPS (63H2).

Infinite

Replace the

HPS (63H2).

31

Page 31