120V Electrical Hook Up

CDVX Series Direct Vent Gas Fireplace

120V Electrical Hook Up

The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in the ab- sence of local codes, with the current CSA C22.1 Canadian Electrical Code.

For USA installations follow local codes and the national electrical code ANSI/ NFPA No. 70.

It is strongly suggested that wiring of the Electrical Junction Box be carried out by a licensed electrician.

Ensure that the power to the supply line has been disconnected before commenc- ing this procedure.

The electrical junction box has been fitted standard on this model to allow for the easy connection of an op- tional fan kit.

To connect the electric box to the house electrical sup- ply follow the steps below.

1.Unscrew the retaining screw holding the electric cover to the outside of the unit. (Fig. 9)

2.Remove the knockout from the electric cover plate.

3.Insert the wire connector through the hole in the electric cover plate and secure.

4.Insert the house wire through the connector on the cover plate.

5.Secure the wires from the receptacle to the incoming line.

6.The receptacle has four wires connected to it. The receptacle is set up for a split system. The top plug of the receptacle is wired separately from the bottom one.

7.Green is ground. White is neutral, Black and red are line voltage to each plug on the receptacle.

INSIDE

Electric Receptacle

OUTSIDE

Electric Receptacle

Cover Plate

FP1597

Fig. 9 Electric receptacle.

General Venting

Your fireplace is approved to be vented either through the side wall, or vertically through the roof.

Only MHSC venting components specifically ap- proved and labelled for this fireplace may be used.

Vent terminations shall not be recessed into a wall or siding.

Horizontal venting which incorporates the twist lock pipe must be installed on a level plane without an inclining or declining slope.

Horizontal venting which incorporates the use of flex venting shall have an inclining slope from the unit of 1” (25 mm) per 24” (610 mm).

There must not be any obstruction such as bushes,

garden sheds, fences, decks or utility buildings within 24” (610mm) from the front of the termination hood.

Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termi- nation area after snow falls, and clear to prevent ac- cidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

Location of Vent Termination

It is imperative the vent termination be located observ- ing the minimum clearances as shown on the next page.

*Check with local codes or in absence of same with CSAB149.1 Installation Codes (1991) for Canada or fol- low the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54 for installations in the USA.

10