Monessen Hearth 36CDVXTRN Maintenance, Cleaning the Standing Pilot Control System, 20012253

Models: 36CDVXTRN

1 44
Download 44 pages 17.07 Kb
Page 36
Image 36
Maintenance

CDVX Series Direct Vent Gas Fireplace

Maintenance

Burner and Burner Compartment

It is important to keep the burner and the burner compartment clean. At least once per year the logs and lava rock/ember material should be removed and the burner compartment vacuumed and wiped out. Remove and refit the logs as per the instructions in this manual.

Always handle the logs with care as they are fragile and may also be hot if the

Cleaning the Standing fireplace has been in use. FK12 Fan Assembly

The fan unit requires periodic cleaning. At least once per month in the operating season open the lower louvre panels and wipe or vacuum the area around the fan to remove any build up of dust or lint.

Cleaning the Standing

Pilot Control System

The burner and control system consist of:

burner

gas orifice

pilot assembly

thermopile

millivolt gas valve

Most of these components may require only an occasional checkup and cleaning and some may require adjustment. If repair is necessary, it should be performed by a qualified technician.

1.Turn off pilot light at gas valve.

2.Allow fireplace to cool if it has been operating.

3.Remove window frame assembly. (Refer to Window Frame Assembly Removal section.)

4.Vacuum burner compartment especially around orifice primary air openings.

5.Visually inspect pilot. Brush or blow away any dust or lint accumulation.

6.Ignite pilot - Refer to Lighting Instructions.

7.Reinstall window frame assembly.

To obtain proper operation, it is imperative that the pilot and burner’s flame characteristics are steady, not lifting or floating.

Typically, the top 3/8” to 1/2” of the thermopile should be engulfed in the pilot flame. (Refer to Page 35, Figure 75)

To adjust pilot burner: (by qualified service technician)

1.Remove pilot adjustment cap

2.Adjust pilot screw to provide properly sized flame.

3.Replace pilot adjustment cap.

The primary air shutter is set at factory and should only be adjusted, if necessary, by a qualified service technician.

36

20012253

Page 36
Image 36
Monessen Hearth 36CDVXTRN Maintenance, Cleaning the Standing Pilot Control System, CDVX Series Direct Vent Gas Fireplace