Monessen Hearth 36CDVXTRN Vertical Sidewall Installations, Vertical Sidewall Applications

Models: 36CDVXTRN

1 44
Download 44 pages 17.07 Kb
Page 23
Image 23
Vertical Sidewall Installations

Vertical Sidewall Applications

Since it is very important that the vent- ing system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The vent graph showing the relationship between verti- cal and horizontal side wall venting will help to deter- mine the various dimensions allowable.

Minimum clearance between vent pipes and combustible materials is one 1” (25 mm) on top, bottom and sides unless otherwise noted.

When the vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must flush up with the siding.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length. The horizontal vent run refer to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

20' (6m)

(2.3m)

Pipe

Straps Every

3’ (914mm)

 

7.5'

Pipe Straps

Every 3’ (914mm)

 

 

Firestop/Zero

 

Clearance Sleeve

FP1012

Fig. 45 Support straps for horizontal runs.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

The maximum number of 90° elbows per side wall installations is three (3).

If a 90° elbow is fitted directly onto the fireplace flange the maximum horizontal vent run before the termination or a vertical rise is 36” (914 mm).

If a 90° elbow is used in the horizontal vent run (level height maintained) the maximum horizontal vent length is reduced by 36” (914 mm). This does not apply if the 90° elbows are used to increase or redirect a vertical rise.

Example: According to the chart the maximum horizontal vent length in a system with a 7.5’ (2.3 m) vertical rise is 20’ (6 m) and if a 90° is required in the horizontal vent it must be reduced to 17’ (5.2 m). In Figure 46, Dimension A plus B must not be

greater than 17’ (5.2 m).

CDVX Series Direct Vent Gas Fireplace

3'

(914mm)

 

 

FP1237

Fig. 46

Maximum horizontal vent run.

 

 

A

 

 

B

 

7.5'

1 x 90° elbow in horizontal plane = 3’ (914mm)

(2.3m)

 

 

 

A + B = 17' (5.2m) Max.

 

 

FP1238

Fig. 47

Maximum vent run with elbows.

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (457 mm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system is 270°. (Fig. 48)

Vertical Sidewall Installations

STEP 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. Page 13, Fig. 17)

For combustible walls first frame in opening.

Combustible Walls: (Fig. 17) Cut a 9³⁄”H x 9³⁄”W (240 x 240 mm) hole through the exterior wall and frame as shown. or 7TCRVT1320 cut a 10³⁄”H x 9³⁄” W (264 x 240 mm) hole.

Noncombustible Walls: (Fig. 17) Hole opening must be 7¹⁄” (190 mm) in diameter.

20012253

23

Page 23
Image 23
Monessen Hearth 36CDVXTRN Vertical Sidewall Installations, Vertical Sidewall Applications, 20012253