9.Install storm collar and seal around the pipe.

Attic Insulation

Shield

Joist

Ceiling

 

11"

Installation

 

11"

Upper Floor

 

Joist

Firestop Spacer

Manual backgroundManual background Nails (4)

CFM100

Fig. 38 Place firestop spacer(s) and secure.

If there is room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed. (Fig. 38)

7.Install roof support (Fig. 39) and roof flashing making sure upper flange is below the shingles. (Fig. 40)

8.Install appropriate pipe sections until the venting is above the flashing. (Fig. 40)

9.Install storm collar and seal around the pipe.

10.Add additional vent lengths for proper height. (Fig 41)

CDVX Series Direct Vent Gas Fireplace

 

 

 

Vent

 

Roof

Termination

 

 

 

 

2’ Min.

Storm Collar

 

 

 

 

 

 

Roof Flash-

 

 

Roof Support

ing

50’

 

Attic Insulation

 

 

Shield

 

(15 m)

 

Attic

 

 

 

 

 

 

Insulation

 

 

 

Joists

 

 

 

 

Joists

 

 

 

FP1022

Fig. 39 Typical straight-up installation.

3 #5 Sheet Metal Screws per Joint

Sealant

Storm Collar

TWL101a

Fig. 40 Roof flashing.

The enlarged ends of the vent section always face down. (Fig. 37)

Min.

2' (610 mm)

FP1185

Fig. 41 Minimum termination to roof clearance.