Monessen Hearth CDV7 fireplace installation, check gas type, installation items needed, 69D3011

Models: CDV7

1 68
Download 68 pages 26.11 Kb
Page 27
Image 27
fireplace installation

fireplace installation

CDVSC7 & CDV7 Series Gas Fireplace

check gas type

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or con- version kit.

Install gas piping to fireplace / burner system location

WARNING

A qualified installer or service person must connect appliance to gas supply. Follow all local codes.

CAUTION

For propane/LP units, never connect fireplace directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP

installation items needed

Before installing fireplace and burner system, make sure you have the items listed below.

External regulator

Piping (check local codes)

Sealant (resistant to propane/LP gas)

 

(supplied by installer)

Equipment shutoff valve*

Test gauge connection*

Sediment trap (recommended)

Tee joint

Pipe wrench

approved flexible gas line with gas connector (if allowed by local codes — not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.

For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 40. Pointing the vent down protects it from freezing rain or sleet.

 

100 lb. (min)

 

Use only new black iron or steel pipe. Internally

 

 

tinned copper or copper tubing can be used

External

Propane/LP

 

Regulator

Supply Tank

CAUTION

per National Fuel Code, Section 2.6.3, providing

 

 

gas meets hydrogen sulfide limits, and where

 

 

permitted by local codes. Gas piping system

 

 

must be sized to provide minimum inlet

 

 

pressure (listed on data plate) at the maximum

 

 

 

 

Vent Pointing

 

flow rate (BTU/hr). Undue pressure loss will

 

 

occur if the pipe is too small.

 

Down

 

 

 

When using copper of flex connectors use only fittings

 

 

approved for gas connections. The gas control inlet is

 

 

3/8" NPT.

 

FP1977

 

 

Figure 40 -

External Regulator with Vent Pointing Down (Propane/LP Only)

69D3011

27

Page 27
Image 27
Monessen Hearth CDV7 fireplace installation, check gas type, installation items needed, occur if the pipe is too small