DFX & DBX Series Vent Free Fireplaces | ELECTRICAL INSTALLATION |
Connect Remote Receiver
THESE INSTRUCTIONS SUPERCEDE THE SECTION ENTITLED “HEARTH MOUNT” IN THE Millivolt
Figure 16
1.Remove bottom louvre door.
2.Connect the remote connectors located in the unit.
3.Stick Velcro• pads with
4.Attach remote receiver to firebox with Velcro• pads. Control switch must face forward.
NOTE: Do not place remote in combustion chamber.
Velcro•
SKY | TECH |
|
|
|
|
|
|
|
|
| |
|
|
|
| FI |
|
| OFF | R |
| REPLACE |
|
|
| EMOTE | MOTE |
| |
|
|
| ON |
| |
|
|
|
|
| |
Remote |
|
|
|
|
|
Receiver |
|
|
| Velcro• |
|
|
|
|
|
| |
Figure 16 - |
|
|
|
|
|
Install Remote Receiver | FP2512 |
Check System Operation
The millivolt system and individual components may be checked with a millivolt meter having a
A.Complete MilliVolt System Check
(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)
a.If the reading is more than 100 millivolts and the automatic valve still does not come on, replace the control.
b.If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading, proceed to Section B below.
B.Thermopile Output Reading Check
(“B” Reading - Thermostat contacts OPEN - Main burner OFF)
1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot voltage, 325 millivolts minimum. If the minimum millivolt reading is not obtainable, replace pilot.
|
| Connect Meter | Switch or | Meter |
Check | To | Leads to | Thermostat | Reading |
Test | Test | Terminals | Contacts | Should Be |
A | Complete | 2 & 3 | Closed | Closed |
| System |
|
|
|
B | Thermopile | 1 & 2 | Open | Open |
|
|
|
|
|
16 | 33D4047 |