VENTING INSTALLATION
Rear Wall Vent installation
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear outside termination behind the appliance
•45° elbows may only be attached to rear when used to direct the flue skyward (to achieve additional rise). Do not attach 45° elbows to rear of appliance in which the flue turns either left or right and terminates horizontal.
•The maximum horizontal distance between the rear of the appliance and the outside face of the outside termination is 20" (508 m). Figure 15
LX Series Direct Vent Gas Fireplace
2.Rigid vent pipes and fittings have special
20"(508 mm)
Maximum
Figure 14 - | DVR584 | |
Rear Vent Application, | ||
| ||
Maximum Horizontal Distance |
|
1.Locate and cut the vent opening in the wall. For com- bustible walls first frame in opening. Figure 15
NOTE: Horizontal runs of vent must be supported every 3' (914 mm). Use wall straps for this purpose.
Figure 16 -
Rigid Vent Pipe Connections
Female
Locking Lugs
Male Slots
FP1953
Combustible Walls: Cut a 11Z\x"H x 9Z\x" W (292 x 24
mm)hole through the exterior wall and frame as shown. Figure 15
Noncombustible Walls: Hole opening should be 7Z\x" (190 mm) in diameter.
Vent Opening for Combustible Walls
3. Attach vent pipe assembly to the fireplace. Set fireplace |
in front of its permanent location to insure minimum |
clearances. Mark the wall for a 11Z\x"H x 9Z\x"W (292 x 24 |
mm) rectangle hole (for noncombustible material such |
as masonry block or concrete, a 7Z\x" [190 mm] diameter |
hole is acceptable). Figure 15. The center of the hole |
should line up with the center line of the horizontal rigid |
9Z\x"
(241 mm)
11Z\x"
(292 mm)
Fireplace Hearth
Framing Detail
vent pipe end. Be sure to allow for minimum rise. Cut |
a 11Z\x" x 9Z\x" (292 X 241 mm) rectangle hole through |
combustible exterior wall (7Z\x" [190 mm] diameter hole |
if noncombustible). Frame as necessary. Allow 1/4" |
minimum rise per foot. Figure 15 |
4. Apply a bead of |
outside edge of vent cap. Position the vent cap in the |
center of hole on the exterior wall with the word “UP” |
on the vent cap facing up. Insure proper clearance of |
1" to combustibles is maintained. Attach the vent cap |
with four wood screws supplied. Figure 17 |
Vent Opening for Noncombustible Wall
NOTE: Replace the wood screws with appropriate fasteners for stucco, brick, concrete, or other types of siding.
7Z\x"
(190 mm)
Figure 15 -Fireplace Hearth
Locate Vent Opening on Wall
| WARNING | Do not recess vent termination into any |
|
| |
|
| wall. This will cause a fire hazard. |
|
|
|
51D0528 | 17 |