VENTING INSTALLATION | LX Series Direct Vent Gas Fireplace |
|
|
3 x 90° |
|
|
|
|
|
Elbows |
|
|
|
| B: 7’ |
|
|
|
| A: 10’ | |
|
|
|
|
| |
3 x 90° |
|
|
| Horizontal 90° Elbow = 3' Reduction | |
Elbows |
|
|
|
| A + B = 17' Maximum |
|
|
|
|
| |
|
|
| 7’6” |
|
|
Figure 20 - |
|
|
|
|
|
Maximum Three (3) 90° Elbows |
|
|
| Figure 22 - | |
Per Installation |
|
|
| Maximum Vent Run with Elbows | |
| FP1176 |
| FP1959 | 90° | |
36" |
|
|
| ||
|
|
|
|
| |
(914 mm) |
|
|
|
|
|
Max. |
|
|
| A | B |
| 36" |
|
|
|
|
| (914 mm) |
|
|
|
|
| Max. |
|
|
|
|
Figure 21 - |
|
|
|
| 7’6” |
|
|
|
| (2.3 m) | |
Maximum Horizontal Run with No Rise | FP1177 |
|
|
| |
Example: According to the vent graph (Page 16) the |
|
| Figure 23 - | ||
|
| Horizontal Run Reduction | |||
maximum horizontal vent length in a system with a 7.5' |
|
| |||
FP2717 |
| ||||
vertical rise is 20’ (6 m). If a 90° elbow is required in the |
| ||||
|
|
| |||
horizontal vent it must be reduced to 17' (5.2 m). |
|
|
|
| |
In Figures 22 and 23, Dimension A plus B must not be |
|
|
| ||
greater than 17' (5.2 m). |
|
|
|
|
|
• The maximum number of 45° elbows permitted per side | 1 + 2 + 3 + 4 = 270° |
| |||
wall installation is two (2). These elbows can be installed |
|
|
| ||
in either the vertical or horizontal run. |
|
|
|
|
|
• For each 45° elbow installed in the horizontal run, the | 1 |
| 1 | ||
length of the horizontal run MUST be reduced by 18" | 2 |
| 2 | ||
(457 mm). This does not apply if the 45° elbows are |
|
| |||
3 |
| 3 | |||
installed on the vertical part of the vent system. |
|
| |||
|
|
| |||
| 4 |
|
| ||
• The maximum number of elbow degrees in a system is |
| 4 | |||
|
| ||||
270°. Figure 24 |
|
|
|
|
|
Example: | Elbow 1 | = | 90° |
|
|
| Elbow 2 | = | 45° |
|
|
| Elbow 3 | = | 45° |
|
|
| Elbow 4 | = | 90° | Figure 24 - |
|
Total Angular Variation | = | 270° | Maximum Elbow Usage |
51D0528 | 19 |