OPERATING INSTRUCTIONS | LX Series Direct Vent Gas Fireplace |
|
|
Lighting pilot for the first time
approved leak testing method
You may check for gas leaks with the following methods only:
•Soap and water solution
•An approved leak testing spray
•Electronic sniffer
WARNING
If using a soap and water solution to test for leaks, DO NOT spray solution onto control body.
DANGER
Never check for gas leak with open flame!
NOTE: Remove any excessive pipe compound from the connections. Excessive pipe compound can set off electronic sniffers.
Check for gas leaks in each of the following locations:
•Pipe from the gas supply line connection to the gas valve
• | Burner connections | • Field made joints / gas shutoff valve | |
• | Pilot | • | Factory made joints |
• Each joint or connection | • | All joints on valve and control body |
Lighting pilot
1.Depress and turn knob counterclockwise to pilot position.
2.Depress fully and hold pilot gas knob. Depress piezo ignitor as many times as needed to ignite the pilot. Keep knob fully depressed for a few seconds. Release and check that pilot continues to burn.
If the pilot does not stay lit, repeat steps 1 and 2.
| O |
T | N |
| |
O |
|
L |
|
I |
|
P |
|
| F |
| F |
| O |
PILOT |
Figure 49 -
Pilot Position
51D0528 | 35 |