NPort 5110 Series User’s Manual

Web Console Configuration

 

Port alias

 

 

 

 

Setting

Factory Default

Necessity

 

 

1 to 15 characters

None

Optional

 

 

(E.g., PLC-No.1)

 

 

 

“Port alias” is included to allow easy identification of the serial devices that are connected to NPort 5110’s serial port.

Serial Parameters

ATTENTION

Check the serial communication parameters in your Serial Device’s user’s manual. You should set up NPort 5110’s serial parameters with the same communication parameters used by your serial devices.

Baud rate

Setting

Factory Default

Necessity

110 bps to 230.4 Kbps

115.2 Kbps

Required

Data bits

 

 

Setting

Factory Default

Necessity

5, 6, 7, 8

8

Required

When the user sets Data bits to 5 bits, the Stop bits setting will automatically change to 1.5 bits.

Stop bits

Setting

Factory Default

Necessity

1, 1.5, 2

1

Required

Stop bits will be set to 1.5 when Data bits is

set to 5 bits.

 

Parity

 

 

Setting

Factory Default

Necessity

None, Even, Odd, Space, Mark

None

Required

Flow control

 

 

Setting

Factory Default

Necessity

None, RTS/CTS, DTR/DSR, Xon/Xoff

RTS/CTS

Required

FIFO

 

 

Setting

Factory Default

Necessity

Enable, Disable

Enable

Required

NPort 5110’s serial ports provide a 16-byte FIFO both in the Tx and Rx directions. To prevent data loss during communication, disable the FIFO setting when your serial device does not have a FIFO.

Interface

Model

Port

Settings

Factory Default

Necessity

NPort 5110

1

RS-232

RS-232

Required

5-9

Page 31
Image 31
Moxa Technologies 5110 Series user manual Serial Parameters