Installation of indoor unit

When installing the ceiling concealed type indoor unit, a specially designed return air bellows shall be installed, as shown in Figure 3, Figure 4.

Figure 3

Installing building roof

*0.5m or*5m

A

Ceiling

 

Unit

Return air bellows

Air supply Air outlet duct

Return air

Detail A

 

Figure 4

Air outlet grille

 

Air supply

No obstacles within 1 m

Return air bellows

Unit

Return air

Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to seal the interface closely. Recommend the distance between the air return duct and the wall is more than 150mm.

The distance between air duct outlet and air conditioner outlet is according to the length of actually installed air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air duct is showed below, when connect to short air duct, using low static terminal (terminal color is write), the distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct, using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet could be within 5m at this point.

Figure 5

sling dog

 

joint of air diffuser

 

 

drain piping

 

 

air return duct

 

 

transition

air outlet

air diffuser

air return shutter air duct

duct

 

Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover the drain piping of condensed water to keep warmth.

As figure shown, suspend and install the unit.

Figure 6

M8 broad foundation bolt

 

 

 

 

M8 suspension screw

Unit

 

 

 

M8 broad lock ring

 

 

M8 nut

 

 

 

Figure 5