Installation Procedure
Refrigerant piping
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.
Pipe material and size
Pipe material Phosphorus deoxidized copper seamless pipe (TP2M) for air conditioner
Model |
| AE072FCAKA | AE122FCAKA | AE182FCAKA |
| AE092FCAKA | AE142FCAKA | AE212FCAKA | |
|
|
|
| AE242FCAKA |
Pipe size | Gas side | ÿ9.52 | ÿ12.70 | ÿ15.88 |
(mm) | Liquid side | ÿ6.35 | ÿ6.35 | ÿ9.52 |
|
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22. |
|
The adding procedure shall be aided with a measuring meter | A |
for a specified amount of supplemented refrigerant |
Requirement
Overfilling or underfilling of refrigerant will cause compressor |
|
fault. The amount of the added refrigerant shall be as specified |
|
in the instructions. | Pipe expander |
Connection of refrigerant pipe
Conduct flared connection work to connect all refrigerant pipes.
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
1. Pipe cutting 2. Removing burrs
3.Insertion nut 4. Pipe expansion
Pipe expansion dimensions as follows:
Pipe diameter ÿ | Size A (mm) | |
6.35 mm (1/4") | 0.8 | ~ 1.5 |
9.52 mm (3/8") | 1.0 | ~ 1.8 |
12.7 mm (1/2") | 1.2 | ~ 2.0 |
15.88 mm (5/8") | 1.4 | ~2.2 |
Correct |
|
| Incorrect | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Slope Damage Bur Partial Overlong
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe | Installing torque | Increased installing |
|
O.D.(mm) | torque |
| |
ÿ6.35 | 11.8 | 13.7 (1.4 |
|
ÿ9.52 | 24.5 | 29.4 (3.0 |
|
ÿ12.70 | 49.0 (5.0 | 53.9 (5.5 | |
ÿ15.88 | 78.4 (8.0 | 98.0 (10.0 | |
|
|
| operation |