Installation Procedure

Refrigerant piping

Allowable pipe length and drop

These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.

Pipe material and size

Pipe material Phosphorus deoxidized copper seamless pipe (TP2M) for air conditioner

Model

 

AE072FCAKA

AE122FCAKA

AE182FCAKA

 

AE092FCAKA

AE142FCAKA

AE212FCAKA

 

 

 

 

AE242FCAKA

Pipe size

Gas side

ÿ9.52

ÿ12.70

ÿ15.88

(mm)

Liquid side

ÿ6.35

ÿ6.35

ÿ9.52

 

Supplementary refrigerant

The refrigerant supplementation shall be as specified in the installation instructions

attached with the outdoor unit. The added refrigerant shall be R22.

 

The adding procedure shall be aided with a measuring meter

A

for a specified amount of supplemented refrigerant

Requirement

Overfilling or underfilling of refrigerant will cause compressor

 

fault. The amount of the added refrigerant shall be as specified

 

in the instructions.

Pipe expander

Connection of refrigerant pipe

Conduct flared connection work to connect all refrigerant pipes.

Pipe cutting and expanding

If the pipe is too long or the flare is damaged, it needs to be cut or expanded.

1. Pipe cutting 2. Removing burrs

3.Insertion nut 4. Pipe expansion

Pipe expansion dimensions as follows:

Pipe diameter ÿ

Size A (mm)

6.35 mm (1/4")

0.8

~ 1.5

9.52 mm (3/8")

1.0

~ 1.8

12.7 mm (1/2")

1.2

~ 2.0

15.88 mm (5/8")

1.4

~2.2

Correct

 

 

Incorrect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slope Damage Bur Partial Overlong

The connection of indoor unit pipes must use double spanners.

The installing torque shall be as given in the following table.

Connecting pipe

Installing torque

Increased installing

 

O.D.(mm)

(N-m)

torque (N-m)

 

ÿ6.35

11.8 (1.2kgf-m)

13.7 (1.4 kgf-m)

 

ÿ9.52

24.5 (2.5kgf-m)

29.4 (3.0 kgf-m)

 

ÿ12.70

49.0 (5.0 kgf-m)

53.9 (5.5 kgf-m)

Double-spanner

ÿ15.88

78.4 (8.0 kgf-m)

98.0 (10.0 kgf-m)

 

 

 

operation

30