Installation Procedure
Drain pipe
! Caution
In order to drain water normally, the drain pipe shall be processed as specified in the installation manual and shall be thermal insulated to avoid dew generation. Improper hose connection may cause indoor water leakage.
Requirements
The indoor drain pipe shall be thermal insulated.
The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation.
The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be of S type elbow, otherwise abnormal sound will be produced.
The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, suppo- rts shall be provided every 1.5 ñ 2m to prevent wavy form.
Central piping shall be laid out according to the following figure.
Take care not to apply external force onto the drain pipe connection part.
1.5m~2m
| Support |
Insulation | Down slope |
(supplied by the user) | above 1/100 |
To the largest (app. 10cm)
VP30
Down slope above 1/100
Pipe and insulation material
S type elbow
Wall
Outside
Slant
Drain pipe (supplied by the user)
Pipe | Rigid PVC pipe VP31.5mm (internal diameter) |
|
|
Insulation | Foamed PE with thickness above 7mm |
Hose
Drain pipe size: ÿ19.05mm2 (3/4") PVC pipe
The hose is used for adjusting the
The soft end of the hose must be fastened with a hose clamp.
Please apply the hose on horizontal part | Hose | Hose clamp |
sulation treatment:
Wrap the hose and its clamp until to the indoor unit without any clearance with insulating material, as shown in the figure.
Drain confirmation | Subsidiary insulation | Insulation | |
Rigid PVC pipe | |||
|
|
During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.