120V Hard Wire Hookup
The output terminal panel, when suppling single phase 120 volts, will provide two circuits available at 62.5 amps with any two wires plus the ground. (See Figure 10 below.)
240V Hard Wire Hookup
The output terminal panel, when suppling single phase 240 volts, will provide one circuit available at 62.5 amps with two wires plus the ground. (See Figure 11 below.)
Figure 10. Hard Wire Hookup | Figure 11. Hard Wire Hookup |
for 120 Volt | for 240 Volt |
NOTE
When using plural single phase voltages, make sure to balance the load on each of the single phase legs.
PAGE 28 —