General Inspection

Prior to each use, the generator should be cleaned and inspected for deficiencies. Check for loose, missing or damaged nuts, bolts or other fasteners. Also check for fuel, oil, and coolant leaks.

Engine Side (Refer to the Engine Instruction Manual)

Air Cleaner

Every 50 hours: Remove air cleaner element and clean heavy duty paper element with kerosene, or foam element with liquid detergent and hot water. Wrap foam element in a cloth and squeeze dry. For heavy duty paper element, wipe excess kerosene with towel.

Fuel Addition

Add diesel fuel (the grade may vary according to season and locations). Always pour through the mesh filter.

Removing Water from the Fuel Tank

After prolonged use, water and other impurities accumulate in the bottom of the tank. Occasionally remove the drain cock and drain the contents. During cold weather, the more empty volume inside the tank, the easier it is for water to condense. This can be reduced by keeping the tank full as much as possible.

Air Removal

If air enters the fuel injection system of a diesel engine, starting becomes impossible. After running out of fuel, or after disassembling the fuel system, bleed the system according to the following procedure.

To restart after running out of fuel, turn the switch to the “ON” position for 15-30 seconds. Try again, if needed. This unit is equipped with an automatic air bleeding system.

Service Daily

If the engine is operating in very dusty or dry grass conditions, a clogged air cleaner will result. This can lead to

aloss of power, excessive carbon buildup in the combustion chamber in high fuel consumption.

Cleaning the Fuel Strainer

Clean the fuel strainer if it contains dust or water. Remove dust or water in the strainer cap and wash it in gasoline. Securely fasten the fuel strainer cap so that fuel will not leak. Check the fuel strainer every 200 hours of operation or once a month.

DCA-15SPX3 — MAINTENANCE

Check Oil Level

Check the crankcase oil level prior to each use, or when the fuel tank is filled. Insufficient oil may cause severe damage to the engine. Make sure the generator is level. The oil level must be between the two notches on the dipstick as shown in Figure 8, page 29.

Replacing Oil Filter

Detach the oil filter cartridge with a filter wrench.

Apply a film of oil to the gasket for the cartridge.

Screw in the cartridge by hand. When the gasket is in contact with the seal surface, tighten the cartridge one or two more times by hand.

After the oil cartridge has been replaced, the engine oil will drop slightly. Run the engine for a while and check for leaks before adding more oil if needed. Clean excessive oil from engine.

Replacing Fuel Filter

Replace the fuel filter cartridge with new one every 400 hours or so.

Apply fuel oil thinly over the gasket and hand-tighten the cartridge into position.

Vent any air.

Flushing Out Radiator and Replacing Coolant

Open both cocks located at the crankcase side and at the lower part of the radiator and drain coolant. Open the radiator cap while draining. Remove the overflow tank and drain.

Check hoses for softening and kinks. Check clamps for signs of leakage.

Flush the radiator by running clean tap water through radiator until signs of rust and dirt are removed. DO NOT clean radiator core with any objects, such as a screwdriver.

Tighten both cocks and replace the overflow tank.

Replace with coolant (see page 30, Table 5 for mixture).

Close radiator cap tightly.

CAUTION :

Allow engine to cool when flushing out radiator. Flushing the radiator while hot will damage radiator.

PAGE 40 — DCA-15SPX3 GENERATOR— PARTS & OPERATION MANUAL — REV. #2 (09/03/01)

Page 40
Image 40
Multiquip operation manual DCA-15SPX3 Maintenance

DCA-15SPX3 specifications

The Multiquip DCA-15SPX3 is a versatile and robust generator designed for a range of applications, making it an ideal choice for contractors, events, and emergency power needs. With a powerful output of 15 kW, this generator is equipped to handle a variety of electrical loads, providing reliable, consistent power.

One of the standout features of the DCA-15SPX3 is its impressive fuel efficiency, thanks to a quiet-running and high-performance engine. This model is designed with a durable, weather-resistant enclosure that not only protects the generator from harsh environmental conditions but also reduces noise levels, making it suitable for use in residential areas or during events where noise control is essential.

The generator operates on diesel fuel, which is known for its efficiency and longevity compared to gasoline-powered counterparts. The DCA-15SPX3 has a user-friendly control panel, offering easy accessibility to start and stop operations. Additionally, it includes built-in safety features, such as low oil shutdown and overload protection, ensuring that the generator operates safely and efficiently.

The DCA-15SPX3 also incorporates advanced technology like digital automatic voltage regulation (AVR), which provides stable voltage output and reduces the likelihood of damage to sensitive electronics and equipment. This technology ensures that the generator maintains a consistent power supply even as the load varies, enhancing its suitability for both light commercial and heavy industrial applications.

With a compact design, the generator is easy to transport and set up, making it convenient for on-the-go power solutions. It features built-in lifting hooks and is mounted on a robust chassis for better mobility. The unit’s low maintenance requirements further enhance its appeal, allowing users to focus more on their tasks rather than routine upkeep.

Overall, the Multiquip DCA-15SPX3 stands out in the market for its balance of power, efficiency, and ease of use, making it an invaluable asset for professionals requiring dependable power in diverse settings. Whether used for temporary job sites, special events, or as a backup power source, it delivers the performance and reliability expected from a high-quality generator.