DCA-15SPX3 — GENERAL INFORMATION
DCA-15SPX3 3 FAMILIARIZATION
Generator
The MQ Power Model
Control Panel
The control panel is provided with the following:
zOne GFCI 120 volt receptacle, 20 amp
z15 kW Output Terminal (UNV)
zMain Circuit Breaker 65 amps
zGFCI Circuit Breaker 20 amps
zAC Ammeter Indicator
zAC Voltmeter Indicator
zOutput Voltage Adjustment Knob
zEngine Warning Indicator
zEngine Speed Control Lever
zHour Meter
zGround Terminal
Open Delta Excitation System
The
There are four Leads: A, B, C and D. During light loads, the power to the Automatic Voltage Regulator (AVR) is supplied from the leads of B & C, when loads increase, the AVR switches and accepts power from leads A & D. The output of leads A & D increase proportionally with load. This has the effect of adding the voltages of each phase to provide better voltage response during heavy loads.
The connections of the AVR to the AC output windings are for the sole purpose of sensing only. No power is required from these windings.
The
Engine
The
In keeping with MQ Power's policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
The basic controls and indicators for the
PAGE 20 —