Multiquip DCA-15SPX3— MAINTENANCE, Inspection / Maintenance, 10 Hrs, 250 Hrs, 500 Hrs

Models: DCA-15SPX3

1 132
Download 132 pages 50.17 Kb
Page 41
Image 41
INSPECTION / MAINTENANCE

DCA-15SPX3 — MAINTENANCE

Generator Storage

For storage of the generator for over 30 days, the following is required:

z Fill the fuel tank completely.

z Completely drain the oil from the crankcase and refill

with fresh oil.

z Clean all external parts of the generator with a cloth. z Cover the generating set and store in a clean, dry place.

INSPECTION / MAINTENANCE

10 Hrs

250 Hrs

500 Hrs

1000 Hrs

DAILY

 

 

 

 

 

 

 

 

 

 

 

 

Check Engine Fluid Levels

X

 

 

 

 

 

 

 

 

 

 

Check Air Cleaner

X

 

 

 

 

 

 

 

 

 

 

Check Battery Acid Level

X

 

 

 

 

 

 

 

 

 

 

Check Fan Belt Condition

X

 

 

 

 

 

 

 

 

 

 

Check for Leaks

X

 

 

 

 

 

 

 

 

 

 

Check for Loosening of Parts

X

 

 

 

 

 

 

 

 

 

 

Replace Engine Oil and Filter *1

 

X

 

 

 

 

 

 

 

 

 

Clean Air Filter

 

X

 

 

ENGINE

 

 

 

 

 

Drain Bottom of Fuel Tank

 

X

 

 

 

 

 

 

 

 

 

Clean Unit, Inside and Outside

 

X

 

 

 

 

 

 

 

 

 

Change Fuel Filter *2

 

 

X

 

 

Clean Radiator and Check Coolant Protection

 

 

X

 

 

Level

 

 

 

 

 

 

 

 

 

 

 

Replace Air Filter Element

 

 

 

X

 

 

 

 

 

 

 

Change Corrosion Resistor

 

 

 

X

 

 

 

 

 

 

 

Check all Hoses and Clamps

 

 

 

X

 

 

 

 

 

 

 

Clean Inside of Fuel Tank

 

 

 

X

 

 

 

 

 

 

GENERATOR

Measure Insulation Resistance Over 3M ohms

 

X

 

 

 

 

 

 

 

 

*1 Replace engine oil anf filter at 100 hours, first time only.

*2 Replace fuel filter at 250 Hours, first time only.

DCA-15SPX3 GENERATOR — PARTS & OPERATION MANUAL — REV. #2 (09/03/01) — PAGE 41