6.4Additional Navigational Aids

6.4.1Function Key

C TM

FW MURPHY - MVIEW WWW.FWMURPHY.COM SALES@FWMURPHY.COM (918) 317-4100

___________________________________________________

Fn-EXITHOME-HELP ACK-ALARMS SCREEN

REMOTE MODE COMMANDS:

RESET AND RUN/STOP

Fn Key Dialog Box Screen

6.4.2 Help Key

Pressing the Function (Fn) key from any screen will display a dialog box on the bottom half of the screen. All available func- tion key commands will be displayed there. The user can then press a single key for the available commands.

In this case, the user can select from a help screen, the alarms screen or issue a remote mode command. If the Fn key is not followed by another key press in five seconds, function mode will time out and the dialog box will go away restoring the previ- ous screen.

Note: In all cases the Fn key options will be context sensitive. Some options will only be available from certain screens or under certain conditions.

C

TM

 

 

PRESS ANY KEY TO EXIT

 

▼▼ -MOVES SCREEN TO SCREEN

▲▼ -MOVES LINE TO LINE

 

HOME-TOP LINE OF SCREEN

HOME AGAIN-MAIN SCREEN

Help Screen

7.0Communications

7.1Communication Ports

Port 1 (SERIAL)

This is the help screen the user will see by pressing the HOME key from the Fn dialog box or by pressing the Fn key followed by the HOME key from a normal screen.

Port 1 is intended as the primary port for the local device, the C3-3 Display, and should be utilized for C3-3 Display in order for the boot loader mode to properly execute in pass-thru mode.

Interface: Refer to the Sequence of Operations to determine how the communication port has been configured.

Protocol: Modbus (Slave)

Connection: There are three (3) screw terminal connectors for RS485. These are identified as A, B, and SHD.

There are three (3) screw terminal connectors for RS232. These are identified as RX, TX, and DTR.

SHD is common for both ports.

Port 2 (SERIAL)

Interface: Refer to the Sequence of Operations to determine how the communication port has been configured.

INSERT DIAGRAM? RICK NOTES ON PREVIOUS MARKUP Protocol: Modbus (Slave), Proprietary (Binary)

Connection: There are three (3) screw terminal connectors for RS485. These are identified as A, B, and SHD.

There are three (3) screw terminal connectors for RS232. These are identified as RX, TX, and DTR.

SHD is common for both ports.

Modbus Slave Address Configuration: The operator may assign a unique Modbus address to each controller (slave) unit that may be in the system. This allows the master controller to differentiate between the modules. For example, to name the controller address 21, place the shunts on LK1, LK4, and LK16 (1 + 4 +16 = 21). Typically, this configuration is set to (1) by the factory.

CE-05171N page 37 of 44

Page 37
Image 37
Murphy CE-05171N manual Communications, Additional Navigational Aids, Communication Ports